24.02.2017 Views

Structural Concrete - Hassoun

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

620 Chapter 17 Design of Two-Way Slabs<br />

periphery of the columns will have maximum negative bending moments. Considering a strip along<br />

AFB, the strip bends like a continuous beam (Fig. 17.5b), having negative moments at A and B and<br />

positive bending moment at F. This strip extends between the two columns A and B and continues<br />

on both sides of the panel, forming a column strip.<br />

Similarly, a strip along EOG will have negative bending moments at E and G and a positive<br />

moment at O, forming a middle strip. A third strip along DHC will behave similarly to strip AFB.<br />

Therefore, the panel can be divided into three strips, one in the middle along EOG, referred to as the<br />

middle strip, and one on each side, along AFB and DHC, referred to as column strips (Fig. 17.5a).<br />

Each of the three strips behaves as a continuous beam. In a similar way, the panel is divided into<br />

three strips in the other direction, one middle strip along FOH and two column strips along AED<br />

and BGC, respectively (Fig. 17.5e).<br />

Referring to Fig. 17.5a, it can be seen that the middle strips are supported on the column<br />

strips, which in turn transfer the loads onto the columns, A, B, C,andD in this panel. Therefore, the<br />

column strips carry more load than the middle strips. Consequently, the positive bending moment in<br />

each column strip (at E, F, G,andH) is greater than the positive bending moment at O in the middle<br />

strip. Also, the negative moments at the columns A, B, C,andD in the column strips are greater than<br />

the negative moments at E, F, G, andH in the middle strips. The portions of the design moments<br />

assigned to each critical section of the column and middle strips are discussed in Section 17.8.<br />

The extent of each of the column and middle strips in a panel is defined by the ACI Code,<br />

Sections 8.4.1.5 and 8.4.1.6. The column strip is defined by a slab width on each side of the column<br />

centerline, x in Fig. 17.5, equal to one-fourth the smaller of the panel dimensions l 1 and l 2 , including<br />

beams if they are present, where<br />

l 1 = span length, center to center of supports, in the direction moments are being determined<br />

l 2 = span length, center to center of supports, in the direction perpendicular to l 1<br />

The portion of the panel between two column strips defines the middle strip.<br />

17.6 MINIMUM SLAB THICKNESS TO CONTROL DEFLECTION<br />

The ACI Code, Sections 8.3.1.1 and 8.3.1.2, specifies a minimum slab thickness in two-way slabs<br />

to control deflection. The magnitude of a slab’s deflection depends on many variables, including the<br />

flexural stiffness of the slab, which in turn is a function of the slab thickness, h. Byincreasingthe<br />

slab thickness, the flexural stiffness of the slab is increased, and consequently the slab deflection is<br />

reduced [13]. Because the calculation of deflections in two-way slabs is complicated and to avoid<br />

excessive deflections, the ACI Code limits the thickness of these slabs by adopting the following<br />

three empirical limitations, which are based on experimental research. If these limitations are not<br />

met, it will be necessary to compute deflections.<br />

1. For 0.2 2.0,<br />

h = l n(0.8 + f y ∕200,000)<br />

36 + 9β<br />

but not less than 3.5 in.<br />

(f y in psi) h = l n(0.8 + f y ∕1400)<br />

36 + 5β(α fm − 0.2)<br />

(f y in psi) h = l n(0.8 + f y ∕1400)<br />

36 + 9β<br />

(f y in MPa) (17.1)<br />

(f y in MPa) (17.2)

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!