352 Chapter 10 Axially Loaded Columns<br />

Assume no. 3 spiral, a s = 0.11 in. 2 ,andd s = 0.375 in.<br />

ρ s = 0.01152 = 4a s(D ch − d b ) 4(0.11)(17 − 0.375)<br />

=<br />

SD 2 S(17) 2<br />

ch<br />

Spacing s is equal to 2.2 in; use no. 3 spiral at s = 2 in. (as shown in Table 10.2).<br />

Example 10.5<br />

Design a rectangular tied short column to carry a factored axial load of 1765 kN. Use f c ′ = 30 MPa,<br />

f y = 400 MPa, column width (b) = 300 mm, and a steel ratio of about 2%.<br />

Solution SI Units<br />

1. Using Eq. 10.9,<br />

P u = 0.8φA g [0.85f ′ c + ρ g (f y − 0.85f ′ c )]<br />

Assuming a steel percentage of 2%,<br />

1765 × 10 3 = 0.8 × 0.65A g [0.85 × 30 + 0.02(400 − 0.85 × 30)]<br />

A g = 102, 887 mm 2<br />

For b = 300 mm, the other side of the rectangular column is 343 mm. Therefore, use a section<br />

of 300 × 350 mm (Ag = 105,000 mm 2 ).<br />

2. A s = 0.02 × 102,887 = 2057 mm 2 . Choose six bars, 22 mm in diameter (A s = 2280 mm 2 ).<br />

3. Check the axial load strength of the section using Eq. 10.6:<br />

φP n = 0.8φ[0.85f c ′(A g − A st )+A st f y ]<br />

= 0.8 × 0.65[0.85 × 30(105,000 − 2280)+2280 × 400]×10 −3<br />

= 1836 kN<br />

This meets the required P u of 1765 kN.<br />

4. Choose ties 10 mm in diameter. Spacing is the least of (1) 16 × 22 = 352 mm, (2) 48 × 10 =<br />

480 mm, or (3) 300 mm. Choose 10-mm ties spaced at 300 mm. Note: Clear spacing of ties<br />

should be at least 4/3 the nominal maximum size of the aggregate.<br />

SUMMARY<br />

Sections 10.1–10.4<br />

Columns may be tied or spirally reinforced:<br />

{ 0.65 for tied columns<br />

φ =<br />

0.75 for spirally reinforced columns<br />

Also, ρ g must be ≤ 8% and ≥1%.