The requirements <strong>for</strong> walk-in-freezers are similar to those <strong>for</strong> walk-in coolers, except that<br />

more insulation is needed. Freezer units installed with the door opening into a walk-in cooler<br />

eliminate storage space on one wall of the cooler, and access to the freezer can be inconvenient.<br />

All walk-in coolers and freezers should be equipped with recording temperature thermometers<br />

that can be easily read by food service personnel. Alarms should be installed in the engineering<br />

department that alert engineering staff to a problem.<br />

Self-Contained Refrigerators and Freezers<br />

In self-contained units, the refrigeration system is mounted at the top or bottom. Bottommounted<br />

models reduce the amount of convenient space available. A compressor, condenser,<br />

and evaporator of the right size are needed <strong>for</strong> uni<strong>for</strong>m temperature control regardless of the<br />

load. Foamed-in-place or froth-type urethane insulation of 21 ⁄2 inches or more thickness is recommended<br />

<strong>for</strong> walls, ceilings, and doors. A one-piece, durable, seamless lining in the interior<br />

cabinet is needed to allow <strong>for</strong> easy cleaning. Exterior finishes vary among manufacturers; vinyl<br />

in a choice of colors, stainless steel, and other durable metals are used.<br />

Refrigerators and storage freezers are designed as reach-in or pass-through and roll-in or<br />

roll-through units, which are convenient in areas between production and service. Solid or glass<br />

doors may be hinged on the right or left. One-piece molded door gaskets that provide a positive<br />

seal are recommended to conserve energy. Full- and half-door models with self-closing and<br />

safety-stop features are available. A system <strong>for</strong> locking all doors is needed <strong>for</strong> security. An exterior<br />

dial thermometer and audiovisual temperature alarm should be installed in all units.<br />

Adjustable legs facilitate leveling of reach-in and pass-through cabinets. Single units may be<br />

equipped with casters <strong>for</strong> mobility. Other design options include provisions <strong>for</strong> interchangeable<br />

interiors that accommodate adjustable rustproof wire shelving, tray or pan slides, roll-out<br />

shelves and drawers, and flush-with-floor models <strong>for</strong> mobile carts and food service racks.<br />

Quick-Chill and Freezing Systems<br />

Refrigeration systems capable of chilling precooked foods to 41°F (5°C) in less than four hours<br />

are available in one- or two-section roll-in units. Rapid chilling is accomplished by circulating<br />

fans installed within the cabinet. High-velocity air, <strong>for</strong>ced horizontally over the surfaces of the<br />

food product, eliminates the <strong>for</strong>mation of layers of warm air that can slow heat transfer.<br />

Self-contained or remote quick-chill models can be purchased. Cabinet finishes, insulation<br />

materials and thickness, door gaskets, hinges, locks, and other features are similar to those<br />

found in conventional storage refrigerators. One model automatically reverts to a 38°F (3°C)<br />

storage refrigerator at the end of the quick-chilling process. Standard equipment includes a chill<br />

timer and several temperature probes. An external probe selector switch, temperature indicator,<br />

and audiovisual alarms should be requested.<br />

<strong>Food</strong>s can be frozen by blast or cryogenic freezing systems. Self-contained roll-in models<br />

or large chambers with a conveyor belt are available. In blast freezing, the product’s temperature<br />

is lowered to 0°F (–18°C) or lower by high-velocity circulating air and a mechanical refrigeration<br />

system. In cryogenic freezing, liquid nitrogen or carbon dioxide in a liquid or gaseous<br />

state and moving air quickly remove heat from the product. The design and construction features<br />

of the cabinet are similar to those of other refrigeration systems. Comparisons of the<br />

capabilities of the mechanical parts used to lower temperatures and the time required in various<br />

models should be made be<strong>for</strong>e selecting a freezer.<br />

Tempering Refrigerators<br />

<strong>Food</strong> service departments that use mostly frozen foods should consider specialized equipment<br />

<strong>for</strong> tempering (thawing) foods rapidly. Conventional refrigeration systems require a great deal of<br />

time <strong>for</strong> this process. Individual units are designed to thaw foods rapidly by using high-velocity<br />

airflow and a system of heating and refrigeration. Products are safe throughout the process<br />

because the cabinet air temperature never exceeds 45°F (7°C). When the tempering process is completed,<br />

the cabinet may be operated as a conventional refrigerator. Conventional refrigerator