Transend - Appendix 5 Renewal capital expenditure - Australian ...
Transend - Appendix 5 Renewal capital expenditure - Australian ...
Transend - Appendix 5 Renewal capital expenditure - Australian ...
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
1 BACKGROUND<br />
0BInvestment Evaluation Summary<br />
TNM-GS-809-0720<br />
Farrell Substation was established in 1982 to provide a connection point for the Pieman River power development and is<br />
a critical node in the Tasmanian transmission network. It connects up to 618 MW of generation to the Tasmanian power<br />
system and, in turn, the national electricity grid via Basslink. Under certain generation scenarios, Farrell Substation can<br />
transmit up to one third of Tasmania’s generation requirement. In addition, the substation is critical to providing a secure<br />
and reliable electricity supply to customers located on the west coast of Tasmania. The load supplied from Farrell<br />
Substation is predominantly for mining and minerals processing and in 2007 the maximum demand was approximately<br />
70 MW.<br />
Farrell Substation is located on Tasmania’s remote west coast and is frequently exposed to inclement weather conditions.<br />
On a number of occasions each year, the substation can not be accessed by road because of snow and ice. In addition, the<br />
substation is approximately two hours drive from the nearest fault response centre. Therefore, adequate remote control<br />
and monitoring facilities are essential to ensuring the security, reliability and availability of the transmission network.<br />
The two existing bus bar protection schemes (one each on the 220 kV and 110 kV) were commissioned in 1983 as part of<br />
the original substation development. The protection relays are now 25 years old and are well beyond their nominal<br />
service life of 15 years. They are Brown Boveri type INX2 static low impedance schemes and are the only bus bar<br />
protection schemes of this type in <strong>Transend</strong>’s transmission network.<br />
2 PROJECT OVERVIEW<br />
This project comprises the replacement of the 220 kV and 110 kV bus bar protection schemes at Farrell Substation. The<br />
bus bar protection schemes will be replaced with new duplicate schemes on both the 110 kV and 220 kV bus bars.<br />
The new bus bar protection schemes will be installed in the existing relay room at Farrell Substation. New multi-core<br />
cabling will be required within the relay room to connect the new panels to Current Transformer, trip, control, AC/DC<br />
supplies, disconnector imaging and SCADA circuits. The project also includes the installation of a small quantity of<br />
cabling from the switchyard to the control building, but it does not include provision for new multi-core cabling between<br />
assets located in the switchyard. Preliminary investigations indicate that there is sufficient spare capacity in the existing<br />
multi-core cabling to accommodate the requirement for additional signalling from the primary plant. It may be a<br />
requirement to utilise or install auxiliary relays if detailed designs identify that there are insufficient spare cable cores.<br />
The 220 kV bus bar protection scheme will need to accommodate ten substation bays: A4 (transformer T1), B4<br />
(transformer T2), H1 (Sheffield–Farrell No. 1 transmission line), J1 (Sheffield–Farrell 220 kV No. 2 transmission line) ,<br />
D1 (Farrell–Reece No. 1 transmission line), E1 (Farrell–Reece No. 2 transmission line), A1 (Farrell–Tribute<br />
transmission line), B1 (Farrell–John Butters transmission line), (Farrell–Bastyan transmission line), and A7 (bus coupler<br />
bay).<br />
The 110 kV bus bar protection scheme will need to accommodate seven substation bays: A5 (transformer T1), B5<br />
(transformer T2), N1 (Farrell–Que-Savage River–Hampshire transmission line), S1 (Farrell–Rosebery transmission line),<br />
T1 (Farrell–Rosebery–Queenstown transmission line), P1 (Farrell–Mackintosh transmission line) and B7 (bus coupler<br />
bay).<br />
3. INVESTMENT TIMING<br />
The Farrell Substation bus bar protection replacement project has been programmed to commence in early 2009, with<br />
final commissioning in June 2010. The project has been attributed a high priority because of the high likelihood and<br />
impact of critical protection scheme failures.<br />
NPV analysis demonstrates that it is most efficient to start this project in 2009.<br />
The 110 kV bus zone has proven more unreliable than the 220 kV system, so it is proposed to undertake works on this<br />
system first. The project is proposed to be staged as follows:<br />
1. Commission the new 110 kV Bus Zone Protection B scheme (GE Multilin type B90), maintaining the existing<br />
Brown Boveri type INX2 scheme in service. Use the existing spare protection CT of bays for new bus bar<br />
protection scheme<br />
© <strong>Transend</strong> Networks Pty Ltd 3 of 10