Current<br />

transformer make /<br />

type<br />

Modern Products<br />

09931<br />

Number<br />

of units<br />

Average<br />

age<br />

(years)<br />

Reyrolle 015204 9 52<br />

<strong>Renewal</strong> Capital Expenditure<br />

TNM-GR-809-0929<br />

Issue 1.0, January 2009<br />

Page 18 of 28 © <strong>Transend</strong> Networks Pty Ltd<br />

UNCONTROLLED WHEN PRINTED<br />

Comment<br />

6 34 These units will be retained as spares.<br />

Tyree 06/123/16 6 30 The condition of these units will be assessed and if<br />

deemed serviceable, they will be installed elsewhere<br />

in the transmission network.<br />

Table 5 – Replacement of voltage transformer makes and types<br />

Voltage transformer<br />

make / type<br />

Number<br />

of units<br />

Average<br />

age<br />

(years)<br />

Asea EMFA 120 12 47<br />

Comment<br />

Balteau UEV110 6 31 These units will be disposed of because of specific<br />

design issues.<br />

Ducon PD 6 46<br />

Haefely Trench VEOT<br />

123<br />

6 22 The condition of these units will be assessed and if<br />

deemed serviceable, they will be installed elsewhere<br />

in the transmission network.<br />

Trench 123/3 24 9 There units were installed at Creek Road Substation<br />

because of the need to replace units that were in<br />

extremely poor condition and highly susceptible to<br />

explosive failure. The condition of these units will<br />

be assessed and if deemed serviceable, they will be<br />

installed elsewhere in the transmission network.<br />

Reyrolle KP5323 1 57<br />

Ritz OTEF 6 12 The condition of these units will be assessed and if<br />

deemed serviceable, they will be installed elsewhere<br />

in the transmission network.<br />

1.6.4 Disconnectors and post insulators<br />

The vast majority of the disconnector types associated with the 110 kV substation redevelopments<br />

are of an obsolete design that comprises many component that are in poor condition, primarily<br />

because of extensive mechanical wear over time. Many of them also have multi-piece, porcelain<br />

post insulators installed that are susceptible to failure, particularly those installed in harsh service<br />

environments. Multi-piece post insulators are susceptible to surface erosion and cracking or<br />

breaking of insulator sheds. Over time, deterioration reduces the mechanical and electrical integrity<br />

of the insulator, leading to mechanical and electrical failure.