Current<br />
transformer make /<br />
type<br />
Modern Products<br />
09931<br />
Number<br />
of units<br />
Average<br />
age<br />
(years)<br />
Reyrolle 015204 9 52<br />
<strong>Renewal</strong> Capital Expenditure<br />
TNM-GR-809-0929<br />
Issue 1.0, January 2009<br />
Page 18 of 28 © <strong>Transend</strong> Networks Pty Ltd<br />
UNCONTROLLED WHEN PRINTED<br />
Comment<br />
6 34 These units will be retained as spares.<br />
Tyree 06/123/16 6 30 The condition of these units will be assessed and if<br />
deemed serviceable, they will be installed elsewhere<br />
in the transmission network.<br />
Table 5 – Replacement of voltage transformer makes and types<br />
Voltage transformer<br />
make / type<br />
Number<br />
of units<br />
Average<br />
age<br />
(years)<br />
Asea EMFA 120 12 47<br />
Comment<br />
Balteau UEV110 6 31 These units will be disposed of because of specific<br />
design issues.<br />
Ducon PD 6 46<br />
Haefely Trench VEOT<br />
123<br />
6 22 The condition of these units will be assessed and if<br />
deemed serviceable, they will be installed elsewhere<br />
in the transmission network.<br />
Trench 123/3 24 9 There units were installed at Creek Road Substation<br />
because of the need to replace units that were in<br />
extremely poor condition and highly susceptible to<br />
explosive failure. The condition of these units will<br />
be assessed and if deemed serviceable, they will be<br />
installed elsewhere in the transmission network.<br />
Reyrolle KP5323 1 57<br />
Ritz OTEF 6 12 The condition of these units will be assessed and if<br />
deemed serviceable, they will be installed elsewhere<br />
in the transmission network.<br />
1.6.4 Disconnectors and post insulators<br />
The vast majority of the disconnector types associated with the 110 kV substation redevelopments<br />
are of an obsolete design that comprises many component that are in poor condition, primarily<br />
because of extensive mechanical wear over time. Many of them also have multi-piece, porcelain<br />
post insulators installed that are susceptible to failure, particularly those installed in harsh service<br />
environments. Multi-piece post insulators are susceptible to surface erosion and cracking or<br />
breaking of insulator sheds. Over time, deterioration reduces the mechanical and electrical integrity<br />
of the insulator, leading to mechanical and electrical failure.