0BInvestment Evaluation Summary<br />

TNM-GS-809-0720<br />

Details of each disconnector type can also be found in the Extra High Voltage Disconnector and Earth Switch Asset<br />

Management Plan (TNM-PL-809-0606).<br />

4.3.1 ACELEC TYPE HDB5L<br />

The Acelec disconnectors are in poor condition and are susceptible to thermal failure of the conductive braids. This type<br />

of disconnector is difficult to maintain due to a complex fixed contact arrangement. In addition, a number of<br />

disconnectors are mounted on girders and/or underhung approximately 10 metres above ground level, requiring<br />

additional resources to maintain.<br />

Any spares required to sustain this type of disconnector in service need to be locally manufactured or salvaged from<br />

decommissioned units.<br />

The current rating of the type HDB5L disconnectors is 800 Amps, resulting in disconnectors D129, E129 and K129 at<br />

Creek Road Substation being circuit limiting equipment, however this limitation currently does not constrain the<br />

associated transmission circuits.<br />

4.3.2 ESSANTEE TYPE 05552<br />

The Essantee disconnectors are in very poor condition and need to be replaced. The units are susceptible to thermal<br />

failure of the conductive braids. The disconnectors have also experienced failures of the operating linkage, preventing<br />

the disconnector from operating; seizing of pivot joints, preventing contacts and disconnector from closing; and contact<br />

misalignment due to weakened springs and worn pivot joint assemblies.<br />

The Essantee disconnectors are designed for operation at 88 kV and do not provide the required electrical clearances for<br />

compliant operation at 110 kV.<br />

4.3.3 STANGER TYPE TTT<br />

The Stanger disconnectors are in poor condition and need to be replaced. The units are an obsolete design, do not have<br />

available spare parts and have exceeded their assigned service life.<br />

4.3.4 TAPLIN TYPE D751<br />

The Taplin disconnector A429 at Creek Road Substation is in acceptable condition. However, the unit is mounted on a<br />

girder approximately 10 metres above ground level and requires additional resource effort to maintain. The unit will be<br />

retained for spares.<br />

4.4 VOLTAGE TRANSFORMERS<br />

The 110 kV voltage transformers installed at Creek Road Substation comprises the following types:<br />

� Balteau type UEV110 - three units (average age of 29 years); and<br />

� Trench type 123/3 units - 18 units (average age of 9 years).<br />

In 2000, a number of 110 kV voltage transformers (Brown Boveri TMZF and Asea Type EMFA) that were in extremely<br />

poor condition were replaced to eliminate the likelihood of explosive failure and to sustain the performance of the<br />

substation prior to the redevelopment of Creek Road Substation 110 kV. The replacement units were manufactured by<br />

Trench and are in acceptable condition. The units will be assessed for their suitability for redeployment elsewhere in the<br />

transmission network following their decommissioning as part of the redevelopment project.<br />

The Balteau 110 kV voltage transformers are of an obsolete design and are in poor electrical condition. They have high<br />

percentage power factor readings, which indicate excessive moisture in the insulating oil and likely degradation of the<br />

winding insulation. While <strong>Transend</strong> has not experienced any major failures of Balteau voltage transformers, other<br />

<strong>Australian</strong> transmission companies have reported explosive failures of Balteau voltage transformers of a similar design.<br />

The explosive failure of a voltage transformer presents a major safety risk to employees and contractors working in the<br />

vicinity of the voltage transformer at the time of failure.<br />

The Voltage Transformer Asset Management Plan (TNM-PL-809-00614) recommends that the units should be<br />

progressively replaced over the next five years.<br />

© <strong>Transend</strong> Networks Pty Ltd 6 of 17