� improves the operational flexibility of the site;<br />
� reduces the overall footprint of the site;<br />
� allows for future expansion of the site; and<br />
� allows for rationalisation of auxiliary equipment.<br />
7.4.3 DRAWBACKS<br />
The drawbacks for this option are that the:<br />
� double-bus bar option is difficult to achieve given site constraints and outage management issues;<br />
0BInvestment Evaluation Summary<br />
TNM-GS-809-0720<br />
� additional temporary works required during implementation to maintain secure and reliable supply at Creek Road<br />
Substation and remote sites; and<br />
� increased risks presented during implementation work within a constrained site.<br />
7.4.4 CONCLUSION<br />
This option is technically viable.<br />
7.5 OPTION 5 - REDEVELOP USING GAS INSULATED SWITCHGEAR<br />
7.5.1 SCOPE<br />
This option includes the replacement, rationalisation and reconfiguration of 110 kV assets at Creek Road Substation<br />
using gas-insulated switchgear (GIS). This option includes redeveloping the site using a double bus arrangement as<br />
presented in Figure 3.<br />
Figure 3 – Option 4: single line diagram (GIS)<br />
CR-NH #1<br />
NN-CR CS-CR #1<br />
T2<br />
X X<br />
X<br />
X<br />
T3 CS-CR #2<br />
X X B/C X X B/C X X B/C X X<br />
Cap Bank 1<br />
(Future)<br />
Cap Bank 2<br />
(Future)<br />
CS-CR-RI<br />
© <strong>Transend</strong> Networks Pty Ltd 15 of 17<br />
X<br />
CS-NH #2<br />
X X<br />
CR-RI<br />
T4