Updated 07/01/03<br />

INT’L<br />

P/N<br />

US<br />

P/N<br />

SU-700iNET<br />

94G4073<br />

SU-700NET<br />

94G3134<br />

SU-1000iNET<br />

94G4074<br />

SU-1000NET<br />

94G3135<br />

Tower Rack Mounted<br />

SU-1400iNET<br />

94G4075<br />

SU-1400NET<br />

94G3136<br />

SU-2200iNET<br />

94G4076<br />

Not<br />

Available<br />

2U<br />

SU-1400RMiB<br />

32P1022 6<br />

2U SU-<br />

1400RMB<br />

32P1020<br />

SU-3000RMiB<br />

94G6677<br />

SU-3000RMB<br />

94G6676<br />

SU-5000RMiB<br />

37L6862<br />

SU-5000RMB<br />

37L6861<br />

UPS Attributes<br />

Communications<br />

Links to Servers<br />

1 1 1 1 1 3 3<br />

Color black black black white black black black<br />

EIA Height<br />

Int’l Models<br />

- - - - 2U 3U 5U<br />

50 or 60Hz, single<br />

phase, VAC: 2, 3 220-240(xxx) 220-240(xxx) 220-240(xxx) 220-240(xxx) 220-240(xxx) 220-240(xxx) 220-240(xxx)<br />

10-Amp, IEC 320-C13<br />

(Device) receptacles<br />

4 4 4 8 4 8 8<br />

16-Amp, IEC 320-C19<br />

(PDU) receptacles<br />

Line Cord Receptacle<br />

(IEC 320-)<br />

US Models<br />

- - - 1 - 1 2<br />

C14 C14 C20 C20 C14 C20 TB 5<br />

50 or 60Hz, single<br />

phase, VAC: 2 120 (120) 120 (120) 120 (120) - 120 (120) 120 (120) 200-220 (208)<br />

Receptacles (NEMA<br />

5-15R)<br />

4 6 6 - 6 8 -<br />

10-Amp, IEC 320-C13<br />

(Device) receptacles<br />

- - - - - - 8<br />

16-Amp, IEC 320-C19<br />

- - - - - - 2<br />

(PDU) receptacles<br />

4<br />

Line Cord Length,<br />

6ft, 5-15P 6ft, 5-15P 6ft, 5-15P - 6ft, L5-15P 6ft, L5-30P 8ft, L6-30P<br />

NEMA Plug<br />

1. Data provided by APC.<br />

2. How-to-Read example for 200-240(208): Input VAC is 200-240 as is the UPS output when electric service is active. When electric service is interrupted and the UPS is on battery, the UPS<br />

output is 208 VAC.<br />

3. Battery output may be set to 220, 225, 230, or 240 VAC.<br />

4. Two PDU jumper cables ship with the UPS for attachment from the IEC 320-C19 receptacles to Power Distribution Units (PDUs) with C20 inlets.<br />

5. SU-5000RMiB (P/N 37L6862) contains a Terminal Block (TB) for direct attachment to an electrical source by qualified personnel.<br />

6. Two IEC power cables are provided to attach devices to the UPS outlets, which are 1.8m long with IEC 320-C13 / C14 connectors.<br />

For the latest product & technical information, refer to the Information Sources on pages 2 and 3.<br />