Chapter 6. MVS-<strong>STX</strong> Inputs <strong>and</strong> Outputs Menu<br />
Setpoint Report<br />
The MVS allows you to view the address <strong>and</strong><br />
channel number of the setpoints of any<br />
channel in the system. Follow this procedure:<br />
1. If in Auto Mode (Auto LED illuminated),<br />
press the Auto/Man Key to put the MVS<br />
in Manual Mode. The Auto LED turns off.<br />
2. Use the Arrow Keys to scroll to the<br />
desired channel.<br />
3. Press the Menu Key to display the Main<br />
Menu. The display shows:<br />
MAIN MENU<br />
Disp I/O Cal<br />
F1 F2 F3<br />
4. Press the F2 Key to access the I/O<br />
Menu. The display shows:<br />
INPUT/OUTPUT MENU<br />
SetPt Iout Serl<br />
F1 F2 F3<br />
5. Press the F1 Key to access the SetPt<br />
Menu. The display shows:<br />
SET POINTS<br />
Set<br />
Report<br />
F1 F2 F3<br />
6. Press the F3 Key to access the<br />
Report Menu. The display flashes a<br />
message stating:<br />
SET POINTS<br />
REPORT ON VES:X<br />
F1 F2 F3<br />
The display then changes to:<br />
SPX Output Chan<br />
Addr YY<br />
7. Press any key other than Esc or Auto/<br />
Man Key to toggle through the setpoints.<br />
8. Press the Esc Key to return to:<br />
SET POINTS<br />
Set<br />
Chan# ZZ<br />
F1 F2 F3<br />
Report<br />
F1 F2 F3<br />
9. Press the Esc Key to scroll up the menu<br />
tree or press the Auto/Man Key to return<br />
to channel monitoring.<br />
Iout (current output)<br />
Current output is typically used to retransmit<br />
continuous weight data to a remote display or<br />
PLC/Distributed Control System (DCS). The<br />
current output setup functions are accessed<br />
in this menu. The functions include adding<br />
<strong>and</strong> deleting current outputs, <strong>and</strong> selecting<br />
fail-safe, net/gross, <strong>and</strong> operating modes.<br />
One current output can be assigned to an<br />
<strong>STX</strong> channel through the current output<br />
capability on the <strong>STX</strong> PCB. Additionally, up to<br />
two current outputs can be assigned to an<br />
<strong>STX</strong> channel through an optional Current<br />
Output PCB in the MVS. The capacity of<br />
each Current Output PCB is 8 current<br />
outputs. The total number of current outputs<br />
in the system is limited only by the number of<br />
Current Output PCBs in the MVS.<br />
The Descriptions section defines each of the<br />
parameters. The Setting Up Current Outputs<br />
on the Current Output PCB, Setting Up<br />
Current Output on the <strong>STX</strong> PCB, <strong>and</strong> Current<br />
Output Report sections provide the<br />
procedures for using the MVS.<br />
Descriptions<br />
Selection of MVS or <strong>STX</strong> in the Iout Menu<br />
determines the PCB for which the current<br />
output is set up:<br />
• MVS — current output is set up on one of<br />
the two available current output channels<br />
on a Current Output PCB in the MVS.<br />
• <strong>STX</strong> — current output is set up on the<br />
one current output channel on the<br />
<strong>STX</strong> PCB.<br />
Once MVS or <strong>STX</strong> is selected the setup is<br />
similar. However, the Add <strong>and</strong> Delete menus<br />
do not appear when setting up current output<br />
on the <strong>STX</strong> PCB.<br />
Set<br />
This menu is used to select current outputs,<br />
assign values to determine the points where<br />
the transmitter outputs the currents, designate<br />
those values as net or gross weights,<br />
<strong>and</strong> define a fail-safe condition for the current<br />
outputs. Set has four submenus:<br />