Appendix B. Serial Comm<strong>and</strong>s<br />

Appendix B. Serial Comm<strong>and</strong>s<br />

Introduction<br />

This appendix contains the serial comm<strong>and</strong>s <strong>and</strong> protocol syntax used for serial communications<br />

between the host or Master (ROPE, PC, etc.) <strong>and</strong> the <strong>STX</strong>. Detailed explanations <strong>and</strong> examples of<br />

the comm<strong>and</strong>s are included.<br />

Note<br />

You must calibrate the <strong>STX</strong> digitally if the <strong>STX</strong> is serially connected to another device, even if<br />

you have already done an analog calibration.<br />

Comm<strong>and</strong> Table<br />

Comm<strong>and</strong> Function Transmitted by Received by<br />

Master to Master from<br />

<strong>STX</strong> 1 <strong>STX</strong> 1<br />

Hex ASCII<br />

23 # K-M product identification number >aa#ssr Addssr<br />

(A3568r for <strong>STX</strong>)<br />

57 W Request engineering units (gross wt) >aaWssr A±dddddddssr<br />

42 B Request engineering units (net wt) >aaBssr A±dddddddssr<br />

54 T Tare addressed vessel >aaTssr Ar<br />

6D,37 m7 Select self-calibration mode >aam7000000dssr Ar<br />

Note: d indicates mode<br />

0=disable periodic self-calibration,<br />

1=enable periodic self-calibration<br />

75,31 u1 Request raw counts >aau1ssr Adddddddssr<br />

6D,31 m1 Select analog or digital mode >aam1000000dssr Ar<br />

Note: d indicates mode<br />

0=analog, 1=digital<br />

4C L Auto lo span calibration >aaLdddddddssr Adssr 2<br />

48 H Auto hi span calibration >aaHdddddddssr Adssr 2<br />

5A Z Auto zero calibration >aaZdddddddssr Adssr 3<br />

Notes:<br />

1<br />

See Table B-2 for definitions of the characters in the comm<strong>and</strong> strings.<br />

2<br />

d is the return status code:<br />

0 = Calibration successful<br />

1 = “Ambiguous” warning. Hi Span counts are greater than Lo Span counts.<br />

2 = “Move more material” warning. Change in weight caused a change of less than 20,000 counts.<br />

Note that the Hi Span or Lo Span value is still entered when the warning (d=1 or 2) is given.<br />

3<br />

d is the return status code:<br />

0 = Calibration successful<br />

Table B-1. <strong>STX</strong> Serial Comm<strong>and</strong>s<br />

B-1