Chapter 6. MVS-<strong>STX</strong> Inputs <strong>and</strong> Outputs Menu<br />
11. The display looks like this:<br />
Addr XX CHAN# YY<br />
420mA*<br />
020mA<br />
F1 F2 F3<br />
(Asterisk indicates the current selection.)<br />
12. Press the F1 Key for the current output<br />
range to be 4 to 20 mA or the F3 Key for<br />
0 to 20 mA. The display acknowledges<br />
the selection <strong>and</strong> returns to:<br />
CURRENT OUTPUT<br />
Set Mode Rprt<br />
F1 F2 F3<br />
13. Press the F1 Key to access the Set<br />
Menu. If you added one output, proceed<br />
to Step 14. If you added two outputs, the<br />
display looks like this:<br />
SELECT OUTPUT<br />
X/20#1<br />
Y/20#2<br />
F1 F2 F3<br />
A ‘4’ or ‘0’ will be in place of the ‘X’ <strong>and</strong><br />
‘Y.’ Press the F1 Key to set up output #1<br />
or the F3 Key to set up output #2.<br />
14. The display looks like this:<br />
SET:<br />
XmA<br />
A ‘4’ or a ‘0’ will be in place of the ‘X.’<br />
15. Press the F1 Key to access 4/0mA. The<br />
display looks like this:<br />
X/20#Y LO VALUE<br />
A ‘4’ or a ‘0’ will be in place of the ‘X.’<br />
(Units are consistent with Units Menu.)<br />
16. Use the keypad or Arrow Keys to input a<br />
value for the weight where you want the<br />
current transmitter to output 4 mA (0 mA<br />
if applicable). Press the Enter Key.<br />
The display acknowledges the entry <strong>and</strong><br />
returns to:<br />
SET:<br />
XmA<br />
20mA<br />
F1 F2 F3<br />
> 0 lbs<br />
F1 F2 F3<br />
20mA<br />
F1 F2 F3<br />
17. Press the F3 Key to access 20mA. The<br />
display looks like this:<br />
X/20#Y HI VALUE<br />
18. Use the keypad or Arrow Keys to input a<br />
value for the weight where you want the<br />
current transmitter to output 20 mA.<br />
Press the Enter Key. The display acknowledges<br />
the entry <strong>and</strong> returns to:<br />
SET:<br />
XmA<br />
F1 F2 F3<br />
19. Press the Menu Key to access the<br />
menu’s second page. The display shows:<br />
SET:<br />
Net/Grs<br />
22. Press the F3 Key to select Fsafe. The<br />
display shows:<br />
FAIL-SAFE MODE?<br />
Lo* Hi NC<br />
F1 F2 F3<br />
(Asterisk indicates the current selection.)<br />
23. Press the F1, F2, or F3 Key to select the<br />
desired fail-safe condition. The display<br />
acknowledges the selection <strong>and</strong><br />
returns to:<br />
SET:<br />
Net/Grs<br />
FSafe<br />
F1 F2 F3<br />
20. Press the F1 Key to access Net/Grs.<br />
The display shows:<br />
SELECT OPERATION<br />
Net<br />
*Gross<br />
F1 F2 F3<br />
(Asterisk indicates the current selection.)<br />
21. Press the F1 Key to select Net or the F3<br />
Key to select Gross. The display acknowledges<br />
the selection <strong>and</strong> returns to:<br />
SET:<br />
Net/Grs<br />
20mA<br />
FSafe<br />
F1 F2 F3<br />
FSafe<br />
F1 F2 F3<br />
24. Press the Esc Key to return to the<br />
Current Output Menu <strong>and</strong> repeat Steps<br />
10 through 23 to set up additional outputs<br />
if desired.<br />
25. Press the Esc Key to scroll up the menu<br />
tree or press the Auto/Man Key to return<br />
to channel monitoring.<br />
> 9999 lbs<br />
F1 F2 F3<br />
A ‘4’ or a ‘0’ will be in place of the ‘X.’<br />
(Units are consistent with Units Menu.)<br />
6-8