Appendix B. Serial Comm<strong>and</strong>s<br />

Examples<br />

For each comm<strong>and</strong> below, the general format of the comm<strong>and</strong> is shown above the example.<br />

‘#’ Comm<strong>and</strong> — K-M Product Identification Number<br />

This comm<strong>and</strong> is sent by the master to request the <strong>STX</strong> to send its K-M product identification code<br />

(code is 35 for the <strong>STX</strong>). For this example, the master requests the code from an <strong>STX</strong> at address<br />

01, which returns a code of 35 <strong>and</strong> a checksum of 68.<br />

Request from Master<br />

Response from <strong>STX</strong><br />

>aa#ssr Addssr Format<br />

>01#84r A3568r Example<br />

‘W’ Comm<strong>and</strong> — Engineering Units (gross)<br />

This comm<strong>and</strong> is sent by the master to request the <strong>STX</strong> to send the gross engineering units<br />

(weight, level, etc.). For this example, the master requests the gross weight from an <strong>STX</strong> at<br />

address 01, which returns a gross weight of +7103 <strong>and</strong> a checksum of 86.<br />

Request from Master<br />

Response from <strong>STX</strong><br />

>aaWssr A±dddddddssr Format<br />

>01WB8r A+000710386r Example<br />

‘B’ Comm<strong>and</strong> — Engineering Units (net)<br />

This comm<strong>and</strong> is sent by the master to request the <strong>STX</strong> to send the net engineering units<br />

(weight, level, etc). For this example, the master requests the net weight from an <strong>STX</strong> at<br />

address 01, which returns a net weight of -4466 <strong>and</strong> a checksum of 91.<br />

Request from Master<br />

Response from <strong>STX</strong><br />

>aaBssr A±dddddddssr Format<br />

>01BA3r A-000446691r Example<br />

‘T’ Comm<strong>and</strong> — Tare Addressed Vessel<br />

This comm<strong>and</strong> is sent by the master to request the <strong>STX</strong> to tare the channel. For this example, the<br />

master requests the tare for an <strong>STX</strong> at address 01.<br />

Request from Master<br />

Response from <strong>STX</strong><br />

>aaTssr Ar Format<br />

>01TB5r Ar Example<br />

B-4