<strong>Drive</strong>s Control, continued<br />
Notes<br />
� : P6.24, P6.26, P6.28<br />
� : P6.25, P6.27, P6.29<br />
In systems with mechanical resonances, you can cut out these frequency ranges for stationary operation.<br />
Up to three different frequency ranges can be set.<br />
Parameters<br />
Access<br />
Factory Setting<br />
PNU ID RUN Value/Range Description<br />
(P1.3)<br />
P6.24 509 X — Skip frequency 1, lower value 0.00<br />
0.00–P6.25 Hz —<br />
P6.25 510 X — Skip frequency 1, upper value 0.00<br />
P6.24–P6.4 —<br />
P6.26 511 X — Skip frequency 2, lower value 0.00<br />
0.00–P6.27 Hz —<br />
P6.27 512 X — Skip frequency 2, upper value 0.00<br />
P6.26–P6.4 Hz —<br />
P6.28 513 X — Skip frequency 3, lower value 0.00<br />
0.00–P6.29 Hz —<br />
P6.29 514 X — Skip frequency 3, upper value 0.00<br />
P6.28–P6.4 Hz —<br />
Setting Range for Skip Frequencies<br />
f<br />
Hz<br />
�<br />
�<br />
t<br />
P6.30 759 X — Automatic REAF attempts 3<br />
1–10 Define the permissible number of automatic restarts<br />
(REAF = Restart After Failure)<br />
P6.31 1481 X — Manual mode, primary control source 1<br />
Like P6.1 Assignment of the control levels<br />
Manual mode is activated via parameter P3.37<br />
P6.32 1482 X — Manual mode, primary speed reference 3<br />
Like P6.2 Assignment of setpoint sources<br />
Manual mode is activated via parameter P3.37<br />
P6.33 1483 X — Manual mode, KEYPAD lock<br />
The Start/Stop functions are blocked in Manual mode via the<br />
keypad<br />
1<br />
0 Deactivated<br />
1 Enabled<br />
M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com 85