Parameters<br />
Motor (P7)<br />
For optimal operation, enter the ratings plate information<br />
for the motor here. This information makes up the base<br />
values for the motor controller (electrical reproduction,<br />
see “V/Hz-Characteristic Curve (P11)” on Page 105).<br />
Motor Parameters from Ratings Plate<br />
P7.5 P7.1<br />
230/400V 4.0/2.3A<br />
0.75 kW cos � 0.67<br />
1410 min–1<br />
50 Hz<br />
P7.4<br />
P7.3 P7.6<br />
The motor data is set to the rated operation data for the<br />
frequency inverter and depends on the performance<br />
variables in factory settings.<br />
86 M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com<br />
Switching Type for Motor Stator Windings<br />
When selecting the rating data, take the dependency of the<br />
type of switching on the strength of the feeding input voltage<br />
into account:<br />
● 230V (P7.5) delta circuit A P7.1 = 4A,<br />
● 400V (P7.5) star connection P7.1 = 2.3A.<br />
Circuits (Delta, Star)<br />
U1 V1 W1<br />
W2 U2 V2<br />
U LN = 230V<br />
U1 V1 W1<br />
W2 U2 V2<br />
U LN = 400V<br />
Example: Single-phase connection of the MMX12AA4D8_<br />
frequency inverter to a input voltage of 230V. The<br />
stator winding of the motor is connected in a<br />
delta circuit (motor rated current 4A as per<br />
nameplate in figure on this page).<br />
Required changes for the electrical reproduction<br />
for the motor: P7.1 = 4.0, P7.3 = 1410, P7.4 =<br />
0.67.