PID Controller, continued<br />

PNU ID<br />

Access<br />

RUN Value/Range Description<br />

P9.15 1433 — Hysteresis, upper limit 0.0<br />

0.00–100% The FBV (Feedback Value Check) message P5.1 (2.3) = 25 is<br />

output if the actual value in RUN mode is below the lower limit<br />

value P9.16. It stays active until:<br />

The actual value exceeds the upper limit value P = 9.15<br />

The frequency inverter switches from RUN mode to STOP mode<br />

P9.16 1434 — Hysteresis, lower limit 0.0<br />

0.00–100% See P9.15<br />

P9.17 1435 — PID controller, max. controller deviation 3.0<br />

0.00–100% If the PID controller is activated (P9.1 = 1), and the deviation<br />

between the setpoint and the actual value exceeds the value<br />

entered here, the PID monitoring is activated. Setting at P5.1<br />

(2.3) = 12<br />

P9.18 1475 — PID controller, reference value scaling 1<br />

0.1–32.7 Setpoint display, multiplication of a factor to display<br />

process-adjusted variables<br />

The value is displayed in M1.17<br />

P9.19 1476 — PID controller, process value scaling 1<br />

0.1–32.7 Actual value indication, multiplication factor for displaying<br />

process variables<br />

The value is displayed in M1.18<br />

P9.20 1478 — PID controller, output signal limit 100.0<br />

0.00–100.0% —<br />