PID Controller, continued<br />
PNU ID<br />
Access<br />
RUN Value/Range Description<br />
P9.15 1433 — Hysteresis, upper limit 0.0<br />
0.00–100% The FBV (Feedback Value Check) message P5.1 (2.3) = 25 is<br />
output if the actual value in RUN mode is below the lower limit<br />
value P9.16. It stays active until:<br />
The actual value exceeds the upper limit value P = 9.15<br />
The frequency inverter switches from RUN mode to STOP mode<br />
P9.16 1434 — Hysteresis, lower limit 0.0<br />
0.00–100% See P9.15<br />
P9.17 1435 — PID controller, max. controller deviation 3.0<br />
0.00–100% If the PID controller is activated (P9.1 = 1), and the deviation<br />
between the setpoint and the actual value exceeds the value<br />
entered here, the PID monitoring is activated. Setting at P5.1<br />
(2.3) = 12<br />
P9.18 1475 — PID controller, reference value scaling 1<br />
0.1–32.7 Setpoint display, multiplication of a factor to display<br />
process-adjusted variables<br />
The value is displayed in M1.17<br />
P9.19 1476 — PID controller, process value scaling 1<br />
0.1–32.7 Actual value indication, multiplication factor for displaying<br />
process variables<br />
The value is displayed in M1.18<br />
P9.20 1478 — PID controller, output signal limit 100.0<br />
0.00–100.0% —<br />
Parameters<br />
Factory Setting<br />
(P1.3)<br />