15.11.2012 Views

M-Maxâ„¢ Series Adjustable Frequency Drive - Eaton Corporation

M-Maxâ„¢ Series Adjustable Frequency Drive - Eaton Corporation

M-Maxâ„¢ Series Adjustable Frequency Drive - Eaton Corporation

SHOW MORE
SHOW LESS

You also want an ePaper? Increase the reach of your titles

YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.

M-Max <strong>Series</strong> Overview<br />

Block Diagram, Elements of M-Max <strong>Frequency</strong> Inverters<br />

L1<br />

L2/N<br />

L3<br />

PE<br />

EMC<br />

Item<br />

Number Description<br />

1 Supply L1, L2/N, L3, PE, input supply voltage ULN = Ue at 50/60 Hz:<br />

MMX11: 100V class, single-phase input connection (1 AC 120V)<br />

MMX12: 200V class, single-phase input connection (1 AC 230V/240V)<br />

MMX32: 200V class, three-phase input connection (3 AC 230V/240V)<br />

MMX34: 400V class, three-phase input connection (3 AC 400V/480V)<br />

MMX35: 575V class, three-phase input connection (3 AC 575V)<br />

2 Internal interference suppression filter (MMX…F_), category C2 and C3, to IEC/EN 61800-3<br />

EMC-connection of internal interference suppression filter to PE<br />

3 Rectifier bridge, single-phase (MMX1_) or three-phase (MMX3_), converts the AC voltage of the electrical network into DC voltage<br />

4 DC link with charging resistor, capacitor and switching mode power supply unit<br />

(SMPS = Switching Mode Power Supply):<br />

DC link voltage UDC with single-phase input connection (1 AC): UDC = 1.41 x ULN DC link voltage UDC with three-phase input connection (3 AC): UDC = 1.35 x ULN 5 Inverter. The IGBT based inverter converts the DC voltage of the DC link (UDC ) into a three-phase AC voltage (U2 ) with variable amplitude and<br />

frequency (f2 ). Sinusoidal pulse width modulation (PWM) with V/f control can be switched to speed control with slip compensation<br />

6 Motor connection U/T1, V/T2, W/T3 with output voltage U2 (0–100% Ue ) and output frequency f2 (0–320 Hz) output current (I2 ):<br />

MMX11: 1.7–4.8A<br />

MMX12: 1.7–9.6A<br />

MMX32: 1.7–11A<br />

MMX34: 1.3–14A<br />

MMX35: 1.7–9.0A<br />

100% at an ambient temperature of 122°F (50°C) with an overload capacity of 150% for 60s every 600s and a starting current of 200% for 2s every 20s<br />

7 Keypad with control buttons, LCD display, control voltage, control signal terminals, microswitches, and interface for the PC interface module (option)<br />

8 Braking transistor: connections R+ and R– for external braking resistance (only with three-phase FS2 and FS3 units)<br />

9 Three-phase asynchronous motor, variable speed control of three-phase asynchronous motor for assigned motor shaft power values (P2 ):<br />

MMX11: 0.25–1.1 kW (230V, 50 Hz) or 0.33–1 hp (230V, 60 Hz)<br />

MMX12: 0.25–2.2 kW (230V, 50 Hz) or 0.25–3 hp (230V, 60 Hz)<br />

MMX32: 0.25–2.2 kW (230V, 50 Hz) or 0.25–3 hp (230V, 60 Hz)<br />

MMX34: 0.37–7.5 kW (400V, 50 Hz) or 0.5–10 hp (460V, 60 Hz)<br />

MMX35: 1–7.5 hp (575V, 60 Hz)<br />

14 M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com<br />

+<br />

R+<br />

R–<br />

U/T1<br />

V/T2<br />

W/T3<br />

PE<br />

M<br />

3 ~