Structure of Exception Message<br />
● Address (of the master request)<br />
● Function code (of the master request): MSB is set to 1<br />
(for example, with function code 06 = 1000 0110)<br />
● Data field contains the error code (is described in the<br />
following table)<br />
● CRC<br />
Serial Interface (Modbus RTU)<br />
Error Code Description<br />
Exception Code Meaning Description<br />
01 Illegal function This function is not supported<br />
02 Illegal data address The address was not found<br />
03 Illegal data value The data format is not permissible or is incorrect<br />
04 Slave device error Occurrence of a non-regenerative error while the slave attempted to execute a slave response<br />
06 Slave device busy The slave has received the master request error-free. However, it is engaged in processing a<br />
lengthy command<br />
Example:<br />
Master request that contains a non-existent data address.<br />
Master request: 01 06 0802 0001 EBAA (hex)<br />
hex Name<br />
01 Slave address<br />
06 Function code (here: Write a holding register)<br />
0802 2050 (dec). The ID number of the written register is<br />
2051 (dec) as the master PLC has an offset of +1<br />
0001 Content (2 bytes) for register 42051:<br />
0000 0000 0000 0001 (bin)<br />
EBAA CRC<br />
Slave response: 01 86 02 C3A1 (hex)<br />
hex Name<br />
01 Slave address<br />
86 Function code (here: Write a holding register)<br />
MSB was set to 1<br />
02 Error code: Stated address not found.<br />
C3A1 CRC<br />
No Slave Response:<br />
In the following cases, the frequency inverter ignores the<br />
request and does not send a reply:<br />
● On receiving a broadcast request<br />
● If the request contains a transmission error<br />
● If the slave address in the request does not match that of<br />
the frequency inverter<br />
● With an invalid data length,<br />
(for example, reading of 12 registers) error message F08 is<br />
triggered in the MMX<br />
● With a CRC or parity error<br />
With a CRC error the value of system parameter S2.1 is<br />
increased by 1 (xx = number of faulty messages)<br />
● If the time interval between the messages is less than<br />
3.5. characters<br />
The master must be programmed to repeat the request if it<br />
does not receive a response within a specified time.<br />
M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com 133