Installation<br />

Connection to Power Section<br />

The following figure shows the general connections for the<br />

frequency inverter in the power section.<br />

Three-Phase Input Connection<br />

3 AC, PE<br />

Connection to Power Section<br />

MMX11_<br />

L1 L2/N L3 U/T1V/T2W/T3<br />

Input<br />

L2/N<br />

L3<br />

PE L1 N<br />

PE<br />

M<br />

3 ~<br />

PES<br />

MMX12_<br />

L1<br />

Input<br />

L2/N<br />

PE L1 N<br />

32 M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com<br />

Terminal Designations in the Power Section<br />

● L1, L2/N, L3: Connection terminals for the supply voltage<br />

(input, input voltage):<br />

● Single-phase AC voltage: connection to L2/N and L3 on<br />

MMX11_<br />

● Single phase AC voltage: Connection to L1 and L2/N<br />

with MMX12_<br />

● Three-phase AC voltage: Connection to: L1, L2/, L3 with<br />

MMX32_, MMX34_ and MMX35_.<br />

● U/T1, V/T2, W/T3: Connection terminals for the<br />

three-phase line to the AC motor (output, frequency<br />

inverter)<br />

● PE: connection for protective ground (reference<br />

potential). PES with mounted cable routing plate for<br />

shielded cables<br />

● R+, R–: Connection terminals for external brake resistance<br />

(only with MMX32_, MMX34_ and MMX35_, output<br />

braking transistor)<br />

MMX32_, MMX34_, MMX35_<br />

L1 L2/N L3<br />

PE L1 L2 L3<br />

Input Output<br />

U/T1 V/T2 W/T3<br />

U1 V1 W1<br />

Ground Connection The ground connection is connected directly with the cable<br />

clamp plates.<br />

PZ2<br />

The shielded cables between the frequency inverter and the<br />

motor should be as short as possible. Connect the shielding<br />

on both ends and over a large surface area with protective<br />

ground PES (Protective Earth Shielding). You can connect the<br />

shielding of the motor cable directly to the cable clamp plate<br />

PE<br />

M4<br />

(360 degrees coverage) with the protective ground.<br />

11.5 lb-in<br />

(1.3 Nm)<br />

The frequency inverter must always be connected to the<br />

ground potential via a grounding cable (PE).<br />

0.17 in<br />

(4.3 mm)<br />

3 ~<br />

Motor