Installation<br />
Connection to Power Section<br />
The following figure shows the general connections for the<br />
frequency inverter in the power section.<br />
Three-Phase Input Connection<br />
3 AC, PE<br />
Connection to Power Section<br />
MMX11_<br />
L1 L2/N L3 U/T1V/T2W/T3<br />
Input<br />
L2/N<br />
L3<br />
PE L1 N<br />
PE<br />
M<br />
3 ~<br />
PES<br />
MMX12_<br />
L1<br />
Input<br />
L2/N<br />
PE L1 N<br />
32 M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com<br />
Terminal Designations in the Power Section<br />
● L1, L2/N, L3: Connection terminals for the supply voltage<br />
(input, input voltage):<br />
● Single-phase AC voltage: connection to L2/N and L3 on<br />
MMX11_<br />
● Single phase AC voltage: Connection to L1 and L2/N<br />
with MMX12_<br />
● Three-phase AC voltage: Connection to: L1, L2/, L3 with<br />
MMX32_, MMX34_ and MMX35_.<br />
● U/T1, V/T2, W/T3: Connection terminals for the<br />
three-phase line to the AC motor (output, frequency<br />
inverter)<br />
● PE: connection for protective ground (reference<br />
potential). PES with mounted cable routing plate for<br />
shielded cables<br />
● R+, R–: Connection terminals for external brake resistance<br />
(only with MMX32_, MMX34_ and MMX35_, output<br />
braking transistor)<br />
MMX32_, MMX34_, MMX35_<br />
L1 L2/N L3<br />
PE L1 L2 L3<br />
Input Output<br />
U/T1 V/T2 W/T3<br />
U1 V1 W1<br />
Ground Connection The ground connection is connected directly with the cable<br />
clamp plates.<br />
PZ2<br />
The shielded cables between the frequency inverter and the<br />
motor should be as short as possible. Connect the shielding<br />
on both ends and over a large surface area with protective<br />
ground PES (Protective Earth Shielding). You can connect the<br />
shielding of the motor cable directly to the cable clamp plate<br />
PE<br />
M4<br />
(360 degrees coverage) with the protective ground.<br />
11.5 lb-in<br />
(1.3 Nm)<br />
The frequency inverter must always be connected to the<br />
ground potential via a grounding cable (PE).<br />
0.17 in<br />
(4.3 mm)<br />
3 ~<br />
Motor