Digital Outputs, continued<br />

PNU ID<br />

Access<br />

RUN Value/Range Description<br />

P5.8 1457 — Current monitoring 0.00<br />

0.00–P7.2 Monitoring of the selected frequency range<br />

(IeA) A monitoring message can be implemented via the digital<br />

outputs (P5.1, P5.2, P5.3 = 27)<br />

P5.9 1458 — DO logic (control signal terminal 13)<br />

Operation of transistor output DO–<br />

0<br />

0 N/O contact<br />

1 N/C contact<br />

P5.10 1331 — RO1 logic (control signal terminals 22, 23)<br />

Operation of relay contact R13/R14<br />

0<br />

0 N/O contact<br />

1 N/C contact<br />

P5.11 1332 — RO2 logic (control signal terminal 24, 25, 26)<br />

Operation of relay changeover contact<br />

0<br />

0 N/O contact (R21–R24) or N/C contact (R21–R22)<br />

1 N/C contact (R21–R24) or N/O contact (R21–R22)<br />

P5.12 1459 — DO, on delay 0.00<br />

0.00–320.00s —<br />

P5.13 1460 — DO, off-delay 0.00<br />

0.00–320.00s —<br />

P5.14 1461 — RO1, on delay 0.00<br />

0.00–320.00s —<br />

P5.15 1424 — RO1, off-delay 0.00<br />

0.00–320.00s —<br />

P5.16 1425 — RO2, on delay 0.00<br />

0.00–320.00s —<br />

P5.17 1426 — RO2, off-delay 0.00<br />

0.00–320.00s —<br />

Parameters<br />

Factory Setting<br />

(P1.3)<br />