M-Maxâ„¢ Series Adjustable Frequency Drive - Eaton Corporation
M-Maxâ„¢ Series Adjustable Frequency Drive - Eaton Corporation
M-Maxâ„¢ Series Adjustable Frequency Drive - Eaton Corporation
You also want an ePaper? Increase the reach of your titles
YUMPU automatically turns print PDFs into web optimized ePapers that Google loves.
Digital Outputs, continued<br />
PNU ID<br />
Access<br />
RUN Value/Range Description<br />
P5.8 1457 — Current monitoring 0.00<br />
0.00–P7.2 Monitoring of the selected frequency range<br />
(IeA) A monitoring message can be implemented via the digital<br />
outputs (P5.1, P5.2, P5.3 = 27)<br />
P5.9 1458 — DO logic (control signal terminal 13)<br />
Operation of transistor output DO–<br />
0<br />
0 N/O contact<br />
1 N/C contact<br />
P5.10 1331 — RO1 logic (control signal terminals 22, 23)<br />
Operation of relay contact R13/R14<br />
0<br />
0 N/O contact<br />
1 N/C contact<br />
P5.11 1332 — RO2 logic (control signal terminal 24, 25, 26)<br />
Operation of relay changeover contact<br />
0<br />
0 N/O contact (R21–R24) or N/C contact (R21–R22)<br />
1 N/C contact (R21–R24) or N/O contact (R21–R22)<br />
P5.12 1459 — DO, on delay 0.00<br />
0.00–320.00s —<br />
P5.13 1460 — DO, off-delay 0.00<br />
0.00–320.00s —<br />
P5.14 1461 — RO1, on delay 0.00<br />
0.00–320.00s —<br />
P5.15 1424 — RO1, off-delay 0.00<br />
0.00–320.00s —<br />
P5.16 1425 — RO2, on delay 0.00<br />
0.00–320.00s —<br />
P5.17 1426 — RO2, off-delay 0.00<br />
0.00–320.00s —<br />
Parameters<br />
Factory Setting<br />
(P1.3)<br />
M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com 79