Digital Inputs, continued<br />

PNU ID<br />

Access<br />

RUN Value/Range Description<br />

P3.6 406 — Ext. fault open (N/C) 0<br />

Like P3.2 Allocation of the function to control signal terminals<br />

Error message when switching off or interrupting<br />

(wire-breakage-safe) the applied control voltage (+24V) from<br />

the assigned control signal terminal (DI1 to DI6)<br />

P3.7 414 — Fault reset 5<br />

Like P3.2 Allocation of the function to control signal terminals<br />

Acknowledges a displayed error message (Reset) when<br />

switching on +24V on the assigned control signal terminal<br />

(DI1 to DI6)<br />

P3.8 407 — Run enable 0<br />

Like P3.2 Allocation of the function to control signal terminals<br />

Rotational direction-independent start release when switching<br />

on +24V on the assigned control signal terminal (DI1 to DI6)<br />

P3.9 419 — Fixed frequency, binary value B0 3<br />

Like P3.2 Allocation of the function to control signal terminals<br />

The binary connection of three digital inputs enable calling<br />

seven fixed frequencies (eight fixed frequencies if parameter<br />

P6.2 = 0 is set)<br />

The limitation of the fixed frequencies is done based on<br />

parameters P6.3 (minimum frequency) and P6.4 (maximum<br />

frequency)<br />

The switch between the individual fixed frequencies is done<br />

with the acceleration time and deceleration times in P6.5<br />

and P6.6<br />

Input (Binary) Fixed <strong>Frequency</strong><br />

B0 B1 B2 (Factory setting)<br />

FF0, P10.1 = 5 Hz,<br />

only if P6.2 = 0<br />

X FF1, P10.2 = 10 Hz<br />

X FF2, P10.3 = 15 Hz<br />

X X FF3, P10.4 = 20 Hz<br />

X FF4, P10.5 = 25 Hz<br />

X X FF5, P10.6 = 30 Hz<br />

X X FF6, P10.7 = 40 Hz<br />

X X X FF7, P10.8 = 50 Hz<br />

Parameters<br />

Factory Setting<br />

(P1.3)<br />

M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com 71