Fixed <strong>Frequency</strong> Setpoint Value<br />

PNU ID<br />

Access<br />

RUN Value/Range Description<br />

P10.1 124 — Fixed frequency FF0 6.00<br />

0.00–P6.4 0.00 Hz up to the maximum frequency value (P6.4)<br />

This value is only active if the setpoint input has been set to<br />

parameter P6.2 = 0<br />

P10.2 105 — Fixed frequency FF1 12.00<br />

0.00–P6.4 0.00 Hz up to the maximum frequency value (P6.4)<br />

In the factory setting, this value can be called directly via DI3<br />

(control signal terminal 10)<br />

P10.3 106 — Fixed frequency FF2 18.00<br />

0.00–P6.4 0.00 Hz up to the maximum frequency value (P6.4)<br />

In the factory setting, this value can be called directly via DI4<br />

(control signal terminal 14)<br />

P10.4 126 — Fixed frequency FF3 24.00<br />

0.00–P6.4 0.00 Hz up to the maximum frequency value (P6.4)<br />

In the factory setting, this value can be called directly by joint<br />

actuation of control signal terminals 10 and 14 (DI3 and DI4)<br />

P10.5 127 — Fixed frequency FF4 30.00<br />

0.00–P6.4 0.00 Hz up to the maximum frequency value (P6.4)<br />

For activation, parameter P3.11 must be assigned a third digital<br />

input. For example, P3.11 = 5: DI5 (control signal terminal 15)<br />

This value can then be called up directly via DI3<br />

Note: In the factory setting, DI5 (control signal terminal 15) is<br />

assigned with the error acknowledgement (Reset). Setting<br />

P3.11 = 0 is recommended<br />

P10.6 128 — Fixed frequency FF5 36.00<br />

0.00–P6.4 0.00 Hz up to the maximum frequency value (P6.4)<br />

For activation, parameter P3.11 must be assigned a third digital<br />

input. For example, P3.11 = 5: DI5 (control signal terminal 15),<br />

see Note on P10.5)<br />

This value can be called directly by joint actuation of control<br />

signal terminals 10 (DI3) and 15 (DI5)<br />

P10.7 129 — Fixed frequency FF6 48.00<br />

0.00–P6.4 0.00 Hz up to the maximum frequency value (P6.4)<br />

For activation, parameter P3.11 must be assigned a third digital<br />

input. For example, P3.11 = 5: DI5 (control signal terminal 15)<br />

see Note on P10.5)<br />

This value can be called directly by joint actuation of control<br />

signal terminals 14 (DI4) and 15 (DI5)<br />

P10.8 130 — Fixed frequency FF7 60.00<br />

0.00–P6.4 0.00 Hz up to the maximum frequency value (P6.4)<br />

For activation, parameter P3.11 must be assigned a third digital<br />

input. For example, P3.11 = 5: DI5 (control signal terminal 15),<br />

see Note on P10.5)<br />

This value can be called directly by joint actuation of control<br />

signal terminals 10 (DI3), 14 (DI4) and 15 (DI5)<br />