Parameters<br />

<strong>Drive</strong>s Control (P6)<br />

In this parameter group (P6), you can define the operating conditions for the M-Max<br />

frequency inverter.<br />

<strong>Drive</strong>s Control<br />

Access<br />

Factory Setting<br />

PNU ID RUN Value/Range Description<br />

(P1.3)<br />

P6.1 125 — Primary remote control source 1<br />

1 Control signal terminals (I/O)<br />

You can switch directly between I/O and KEYPAD with the<br />

LOC/REM button<br />

2 Operating unit (KEYPAD)<br />

The LOC/REM button has no function here<br />

3 Fieldbus (BUS)<br />

You can switch directly between BUS and KEYPAD with the<br />

LOC/REM button<br />

Selecting the control sources can be done directly with the<br />

LOC/REM button between the control source selected in<br />

P6.1 and the operating unit.<br />

During operation (RUN) the drive is always stopped (STOP)<br />

when changing control sources (LOC/REM button).<br />

The control source selected with parameter P6.1 or with the<br />

LOC/REM button is shown on the bottom page in the LCD<br />

display (see figure on this page).<br />

Example: Control Level I/O Activated<br />

READY<br />

80 M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com<br />

REF<br />

MON<br />

PAR<br />

FLT<br />

RUN STOP ALARM FAULT<br />

FWD REV I/O KEYPAD BUS<br />

P6.2 117 — Primary remote speed reference 3<br />

0 Fixed frequency (FF0)<br />

The value can be set in parameter P10.1<br />

1 Operating unit (REF)<br />

This setting causes the setpoint defined at REF to be read.<br />

It can be set via the keypad with the arrow buttons or at<br />

parameter P6.15<br />

2 Fieldbus (BUS)<br />

Setpoint entry via Modbus RTU (control signal terminals A<br />

and B) or optional fieldbus connection (for example, CANopen,<br />

PROFIBUS DP)<br />

3 AI1 (analog setpoint 1)<br />

Voltage set value: 0 (2)–10V at control signal terminal 2<br />

Scaling and filtering: P2.1 to P2.4<br />

4 AI2 (analog setpoint 2)<br />

Current setpoint value: 0 (4) –20 mA to control signal terminal 4<br />

Scaling and filtering: P2.5 to P2.8<br />

5 Motor potentiometer<br />

The actuation is implemented via the digital inputs assigned at<br />

P3.18 and P3.19 (DI1–DI6). The required acceleration and<br />

deceleration times can be set at P6.5 (acc1) and P6.6 (dec1)<br />

Assigning a digital input (DI1–DI6) at P6.20 enables the set<br />

value of the motor potentiometer to be set directly to zero