Digital Inputs, continued<br />

PNU ID<br />

Access<br />

RUN Value/Range Description<br />

P3.22 1409 — PLC program pause 0<br />

Like P3.2 Assignment of control signal terminal<br />

P3.23 1410 — Counter, input signal 0<br />

Like P3.2 Assignment of control signal terminal<br />

Counts the activation of the selected digital input (DI1–DI6)<br />

P3.24 1411 — Counter, reset 0<br />

Like P3.2 Assignment of control signal terminal<br />

Resets the outputs P5.1 = 20, P5.1 = 21 and display value<br />

M1.21 to zero<br />

P3.25 1412 — Activate secondary remote control source 0<br />

Like P3.2 Assignment of control signal terminal<br />

Move between the control levels set at P6.1 and P6.17<br />

(LOC-REM function)<br />

P3.26 1413 — Activate secondary remote speed reference 0<br />

Like P3.2 Assignment of control signal terminal<br />

Switch between the setpoint sources AI1 and AI2 set at<br />

P6.2 and P6.18<br />

P3.27 1414 — Activate second parameter set (2PS) 0<br />

Like P3.2 Assignment of control signal terminal<br />

The values set at the parameter group P14 are activated<br />

P3.28 1415 — Fieldbus, remote input 0<br />

Like P3.2 Assignment of control signal terminal<br />

The assigned digital input is written directly to the general<br />

status word (ID 2102, bit 11)<br />

P3.29 1416 — Counter reference value 1 0<br />

0–65,535 Trigger value for P5.1 = 20<br />

P3.30 1417 — Counter reference value 2 0<br />

0–65,535 Trigger value for P5.1 = 21<br />

P3.31 1418 — DI1 logic (control signal terminal 8)<br />

The logic activates the response of the control signal<br />

terminal (see figure on Page 69)<br />

N/O contact (failsafe) N/C contact<br />

0<br />

0 N/O contact<br />

1 N/C contact<br />

P3.32 1419 — DI2 logic (control signal terminal 9) 0<br />

Like P3.31 Function<br />

Parameters<br />

Factory Setting<br />

(P1.3)<br />