Parameters<br />
PID Controller, continued<br />
PNU ID<br />
Access<br />
RUN Value/Range Description<br />
P9.6 334 — PID controller, actual value (PV) 2<br />
0 Fieldbus<br />
1 AI1 and S2, (see figure on Page 37)<br />
P2.1 = 0 (0 mA/0V)<br />
P2.1 = 1 (4 mA/2V)<br />
2 AI2 and S3, (see figure on Page 37)<br />
P2.5 = 0 (0 mA/0V)<br />
P2.5 = 1 (4 mA/2V)<br />
P9.7 336 — PID controller, actual value limiting, minimum 0.0<br />
0–100% —<br />
P9.8 337 — PID controller, actual value limiting, maximum 100.0<br />
0–100% —<br />
P9.9 340 — PID controller, controller deviation 0<br />
0 Not inverted<br />
1 Inverted<br />
Inverted PID control (P9.9 = 1) is used in applications in which<br />
the feedback value generator supplies an inverted signal<br />
Example: With increasing pressure, a pressure sensor output<br />
signal (+10V…0V = 0…max. bar) drops<br />
P9.10 132 — PID controller, D rate time 0.00<br />
0–10s Differential time constant<br />
P9.11 1431 — PID controller, output filter, delay time 0.0<br />
0.00–10.00s —<br />
P9.12 1016 — Sleep mode, frequency 0.00<br />
0–P6.4 Hz The frequency inverter stops automatically if the frequency of<br />
the drive drops below the sleep level defined by this parameter<br />
for a longer period than the time defined by parameter P9.14<br />
P9.13 1018 — Sleep mode, wake up frequency 25.0<br />
0.00–100% The wake up frequency defines the value below which the<br />
actual value must drop before the RUN mode of the frequency<br />
inverter is restored<br />
P9.14 1017 — Sleep mode, delay time 30<br />
0–3600s This parameter determines the minimum period in which the<br />
frequency inverter must stay below the frequency set at P9.12<br />
before the frequency inverter is stopped<br />
94 M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com<br />
Factory Setting<br />
(P1.3)