Insulation Testing<br />

The M-Max series frequency inverters are tested, delivered<br />

and require no additional testing.<br />

WARNING<br />

On the control signal and the connection terminals of the<br />

frequency inverter, no leakage resistance tests are to be<br />

performed with an insulation tester.<br />

WARNING<br />

Wait at least 5 minutes after switching the supply<br />

voltage off before you disconnect a connection on the<br />

connection terminals (L1, L2/N, L3, U/T1, V/T2, W/T3,<br />

R+, R–) of the frequency inverter.<br />

If insulation testing is required in the power circuit of the<br />

PDS, you must consider the following measures.<br />

Testing the Motor Cable Insulation<br />

Disconnect the motor cable from connection terminals U/T1,<br />

V/T2 and W/T3 of the frequency inverter and from the motor<br />

(U, V, W). Measure the insulation resistance of the motor<br />

cable between the individual phase conductors and between<br />

the phase conductor and the protective conductor.<br />

The insulation resistance must be greater than 1M ohm.<br />

Installation<br />

Testing the Input Cable Insulation<br />

Disconnect the power cable from the input supply network<br />

and from connection terminals L1, L2/N and L3 of the<br />

frequency inverter. Measure the insulation resistance of the<br />

input cable between the individual phase conductors and<br />

between each phase conductor and the protective<br />

conductor.<br />

The insulation resistance must be greater than 1M ohm.<br />

Testing the Motor Insulation<br />

Disconnect the motor cable from the motor (U, V, W) and<br />

open the bridge circuits (star or delta) in the motor terminal<br />

box. Measure the insulation resistance of the individual<br />

motor windings. The measurement voltage must at least<br />

match the rated voltage of the motor but is not to exceed<br />

1000V.<br />

The insulation resistance must be greater than 1M ohm.<br />

Consider the information from the motor manufacturer in<br />

testing the insulation resistance.<br />