Modbus Process Data<br />
Process data is processed in the M-Max frequency inverter faster than the display values,<br />
error codes and parameters.<br />
Input Process Data<br />
The input process data is used to control the M-Max frequency inverter.<br />
Control Word (ID 2001)<br />
These bits are used to control the M-Max frequency inverter. The content can be adapted to<br />
your own application and then sent as a control word to the frequency inverter.<br />
Serial Interface (Modbus RTU)<br />
ID Modbus Register Designation Value Range Type<br />
2001 32001, 42001 Fieldbus control word (BUS) — Binary code<br />
2002 32002, 42002 Fieldbus general control word (BUS) — Binary code<br />
2003 32003, 42003 Fieldbus speed setpoint (BUS) 0.01 %<br />
2004 32004, 42004 PID controller, setpoint 0.01 %<br />
2005 32005, 42005 PID actual value 0.01 %<br />
2006 32006, 42006 — — —<br />
2007 32007, 42007 — — —<br />
2008 32008, 42008 — — —<br />
2009 32009, 42009 — — —<br />
2010 32010, 42010 — — —<br />
2011 32011, 42011 — — —<br />
Description<br />
Bit<br />
Value = 0 Value = 1<br />
0 Stop Operation<br />
1 Clockwise rotating field (FWD) Anticlockwise rotating field (REV)<br />
2 No action Reset error<br />
3 As per setting P6.8 Free coasting (overwrite value from P6.8)<br />
4 As per setting P6.8 Ramp (overwrite value from P6.8)<br />
5 No action Overwrite acceleration/deceleration ramps to 0.1 s<br />
6 No action Block setpoint (speed not variable)<br />
7 No action Overwrite setpoint with 0<br />
8 No action Control level = Fieldbus (overwrite value from P6.8)<br />
9 No action Setpoint input = Fieldbus (overwrite value from P6.8)<br />
10 Not used —<br />
11 Not used —<br />
12 No action The inverter is blocked and the drive stops as quickly as possible<br />
(an edge is required for restart)<br />
13 No action Control of a digital output:<br />
P5.1 = 28 (Relay R01)<br />
P5.2 = 28 (Relay R02)<br />
P5.3 = 28 (Transistor D0)<br />
14 Not used —<br />
15 Not used —<br />
M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com 135