Modbus Process Data<br />

Process data is processed in the M-Max frequency inverter faster than the display values,<br />

error codes and parameters.<br />

Input Process Data<br />

The input process data is used to control the M-Max frequency inverter.<br />

Control Word (ID 2001)<br />

These bits are used to control the M-Max frequency inverter. The content can be adapted to<br />

your own application and then sent as a control word to the frequency inverter.<br />

Serial Interface (Modbus RTU)<br />

ID Modbus Register Designation Value Range Type<br />

2001 32001, 42001 Fieldbus control word (BUS) — Binary code<br />

2002 32002, 42002 Fieldbus general control word (BUS) — Binary code<br />

2003 32003, 42003 Fieldbus speed setpoint (BUS) 0.01 %<br />

2004 32004, 42004 PID controller, setpoint 0.01 %<br />

2005 32005, 42005 PID actual value 0.01 %<br />

2006 32006, 42006 — — —<br />

2007 32007, 42007 — — —<br />

2008 32008, 42008 — — —<br />

2009 32009, 42009 — — —<br />

2010 32010, 42010 — — —<br />

2011 32011, 42011 — — —<br />

Description<br />

Bit<br />

Value = 0 Value = 1<br />

0 Stop Operation<br />

1 Clockwise rotating field (FWD) Anticlockwise rotating field (REV)<br />

2 No action Reset error<br />

3 As per setting P6.8 Free coasting (overwrite value from P6.8)<br />

4 As per setting P6.8 Ramp (overwrite value from P6.8)<br />

5 No action Overwrite acceleration/deceleration ramps to 0.1 s<br />

6 No action Block setpoint (speed not variable)<br />

7 No action Overwrite setpoint with 0<br />

8 No action Control level = Fieldbus (overwrite value from P6.8)<br />

9 No action Setpoint input = Fieldbus (overwrite value from P6.8)<br />

10 Not used —<br />

11 Not used —<br />

12 No action The inverter is blocked and the drive stops as quickly as possible<br />

(an edge is required for restart)<br />

13 No action Control of a digital output:<br />

P5.1 = 28 (Relay R01)<br />

P5.2 = 28 (Relay R02)<br />

P5.3 = 28 (Transistor D0)<br />

14 Not used —<br />

15 Not used —<br />