Setpoint Input (REF)<br />
REF: Setpoint value definition (Reference) via the operating unit.<br />
The settings of the frequency setpoint via the keypad have the same effect as the function of<br />
an electronic motor potentiometer. The set value is written in parameter P6.15 and can also<br />
be changed there. It is retained also with a disconnection of the supply voltage.<br />
A frequency reference value that is set under REF is only effective with the KEYPAD control<br />
level activated.<br />
The following table shows a good example of specifying the frequency setpoint value via the<br />
operating unit.<br />
Setpoint Input (REF)<br />
Sequence Commands Display Description<br />
1 Activate control level KEYPAD with the LOC/REM button.<br />
The arrow ( ) points to menu item REF<br />
LOC<br />
REM<br />
I<br />
REF<br />
MON<br />
PAR<br />
FLT<br />
READY<br />
RUN STOP ALARM FAULT<br />
FWD REV I/O KEYPAD BUS<br />
Parameters<br />
Actuating the START button enables the RUN mode (rotating field<br />
direction FWD)<br />
The STOP button (P6.16 = 1) activates the STOP mode. The Stop<br />
function is set at parameter P6.8<br />
2 READY RUN STOP ALARM FAULT Pressing the OK button activates the setpoint entry (right-hand<br />
segment flashing)<br />
OK<br />
REF<br />
MON<br />
PAR<br />
FLT<br />
FWD REV I/O KEYPAD BUS<br />
The two arrow buttons (< or >) are used to select the entry digit<br />
(cursor)<br />
The arrow buttons or are used to select the value of the entry<br />
digit (0, 1, 2, …9, 0)<br />
Note: Changes in the frequency setpoint are only possible if the<br />
number display is flashing (Hz), even in RUN mode. The value is<br />
stored when the display is constant<br />
When the supply voltage is switched off, the last setpoint entered<br />
(see P6.15) and the KEYPAD mode are stored<br />