Setpoint Input (REF)<br />

REF: Setpoint value definition (Reference) via the operating unit.<br />

The settings of the frequency setpoint via the keypad have the same effect as the function of<br />

an electronic motor potentiometer. The set value is written in parameter P6.15 and can also<br />

be changed there. It is retained also with a disconnection of the supply voltage.<br />

A frequency reference value that is set under REF is only effective with the KEYPAD control<br />

level activated.<br />

The following table shows a good example of specifying the frequency setpoint value via the<br />

operating unit.<br />

Setpoint Input (REF)<br />

Sequence Commands Display Description<br />

1 Activate control level KEYPAD with the LOC/REM button.<br />

The arrow ( ) points to menu item REF<br />

LOC<br />

REM<br />

I<br />

REF<br />

MON<br />

PAR<br />

FLT<br />

READY<br />

RUN STOP ALARM FAULT<br />

FWD REV I/O KEYPAD BUS<br />

Parameters<br />

Actuating the START button enables the RUN mode (rotating field<br />

direction FWD)<br />

The STOP button (P6.16 = 1) activates the STOP mode. The Stop<br />

function is set at parameter P6.8<br />

2 READY RUN STOP ALARM FAULT Pressing the OK button activates the setpoint entry (right-hand<br />

segment flashing)<br />

OK<br />

REF<br />

MON<br />

PAR<br />

FLT<br />

FWD REV I/O KEYPAD BUS<br />

The two arrow buttons (< or >) are used to select the entry digit<br />

(cursor)<br />

The arrow buttons or are used to select the value of the entry<br />

digit (0, 1, 2, …9, 0)<br />

Note: Changes in the frequency setpoint are only possible if the<br />

number display is flashing (Hz), even in RUN mode. The value is<br />

stored when the display is constant<br />

When the supply voltage is switched off, the last setpoint entered<br />

(see P6.15) and the KEYPAD mode are stored<br />

M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com 127