For Modbus to function at least the following parameters must be set:<br />

Another requirement is that the arrow in the lower status line of the LCD display is pointing<br />

to BUS (adjustable via the LOC/REM button). The PLC (master) must also be provided with an<br />

RS485 serial interface and the necessary Modbus RTU driver software.<br />

Operating Mode Modbus RTU<br />

Operating mode Modbus RTU (Remote Terminal Unit) transfers the data in binary<br />

format (faster data rate) and determines the transfer format for the data request and the<br />

data response. Each message byte that is sent contains two hexadecimal characters<br />

(0 … 9, A … F).<br />

The data transfer between a master (PLC) and the frequency inverter (M-Max) is carried out<br />

according to the following sequence:<br />

Master request: the master sends a Modbus frame to the frequency inverter.<br />

Slave response: the frequency inverter sends a Modbus frame as a response to the master.<br />

Data Exchange Between Master and Slave<br />

The frequency inverter (slave) only sends a response if it has received a request from the<br />

master beforehand.<br />

Notes<br />

� Master request.<br />

� Slave response, not with broadcast.<br />

Serial Interface (Modbus RTU)<br />

PNU Value Notes<br />

S2.2 1 To activate Modbus<br />

S2.3 1–255 Set differently at each slave (MMX); 0 is used by the master for broadcasts<br />

S2.4 0–8 Same setting at the master and slave<br />

S2.6 0/1 Same setting at the master and slave<br />

6.1 3 Fieldbus selected as a control level<br />

6.2 2 Set setpoint value via the fieldbus; other setpoint sources also possible, fixed frequencies overlay all<br />

setpoint values, also a fieldbus setpoint value<br />

Master<br />

Start<br />

Address (1 Byte)<br />

Function Code (1 Byte)<br />

Data (N x 1 Byte)<br />

CRC (2 Bytes)<br />

End<br />

Start<br />

Address (1 Byte)<br />

Function Code (1 Byte)<br />

Data (N x 1 Byte)<br />

CRC (2 Bytes)<br />

End<br />

MMX_<br />

(Slave)<br />

M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com 131