Parameters<br />

Filter Time Constant<br />

The filter time constant can be used to filter out disturbance<br />

with analog signals.<br />

In the default setting the filter time constant is active with<br />

0.1 seconds. The time value set here applies to 63% of the<br />

maximum analog signal (+10V, 20 mA).<br />

Long filter times lead to a delay in the analog signal<br />

processing.<br />

You can deactivate the filter time constant by setting the<br />

parameter to 0.0:<br />

P2.4 (AI1) = Filter time constant, analog input AI1<br />

P2.8 (AI2) = Filter time constant, analog input AI2<br />

P4.4 (AO) = Filter time constant, Analog output AO<br />

Filter Time Constant<br />

AI1<br />

AI2<br />

100%<br />

63%<br />

P2.4 AI1<br />

P2.8 AI2<br />

P4.4 AO<br />

t (s)<br />

Notes<br />

� Analog signal with faults (unfiltered).<br />

� Filtered analog signal.<br />

� Filter time constant at 63% of the set value.<br />

68 M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com