PID Controller (P9)<br />
The M-Max series frequency inverters are provided with a<br />
PID controller that you activate with P9.1 = 1. The controller<br />
can be deactivated via a digital input (P3.12).<br />
PID control is superimposed on the frequency inverter<br />
function. You should therefore set all of the frequency<br />
inverter’s drive-related parameters, such as maximum output<br />
frequency (motor speed), acceleration and deceleration<br />
ramps (mechanical load, belts). <strong>Frequency</strong> inverter and motor<br />
are process-integrated actuators. The output frequency to<br />
the motor (which determines the speed) is specified as<br />
manipulated variable from the PID controller.<br />
PID Controller<br />
PNU ID<br />
Access<br />
RUN Value/Range Description<br />
Parameters<br />
When the PID controller is activated, the setpoints and actual<br />
values become process variables and are normalized<br />
automatically into percentages (%). For example, the<br />
specified setpoint (0–100%) here is the same as a volume<br />
flow (0–50 m3 /h). The actual value here is the volume flow<br />
(m3 /h) from a suitable sensor, which is evaluated again as a<br />
percentage (0–100%).<br />
If this process data is to be displayed in the physical variable<br />
(m3 /h), you can set the conversion with parameter P9.19<br />
(see “Display factor (P9.19)”).<br />
P9.1 163 — PID Controller 0<br />
0 Deactivated<br />
1 Activated for drive control<br />
2 Activated for external application<br />
P9.2 118 — PID controllers, P gain 100<br />
0–1000% Proportional Gain (KP)<br />
Low values attenuate the control action<br />
High values can cause oscillation<br />
P9.3 119 — PID controller, I reset time 10.0<br />
0–320s Integral time constant<br />
P9.4 167 — PID controller, keypad reference 0.0<br />
0–100% Setting range<br />
P9.5 332 — PI controller, setpoint source 0<br />
0 The setting range is limited by P6.3 (raised starting frequency)<br />
and P6.4 (end frequency)<br />
Keypad (P9.4)<br />
1 Fieldbus<br />
2 AI1<br />
3 AI2<br />
Factory Setting<br />
(P1.3)<br />
M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com 93