PID Controller (P9)<br />

The M-Max series frequency inverters are provided with a<br />

PID controller that you activate with P9.1 = 1. The controller<br />

can be deactivated via a digital input (P3.12).<br />

PID control is superimposed on the frequency inverter<br />

function. You should therefore set all of the frequency<br />

inverter’s drive-related parameters, such as maximum output<br />

frequency (motor speed), acceleration and deceleration<br />

ramps (mechanical load, belts). <strong>Frequency</strong> inverter and motor<br />

are process-integrated actuators. The output frequency to<br />

the motor (which determines the speed) is specified as<br />

manipulated variable from the PID controller.<br />

PID Controller<br />

PNU ID<br />

Access<br />

RUN Value/Range Description<br />

Parameters<br />

When the PID controller is activated, the setpoints and actual<br />

values become process variables and are normalized<br />

automatically into percentages (%). For example, the<br />

specified setpoint (0–100%) here is the same as a volume<br />

flow (0–50 m3 /h). The actual value here is the volume flow<br />

(m3 /h) from a suitable sensor, which is evaluated again as a<br />

percentage (0–100%).<br />

If this process data is to be displayed in the physical variable<br />

(m3 /h), you can set the conversion with parameter P9.19<br />

(see “Display factor (P9.19)”).<br />

P9.1 163 — PID Controller 0<br />

0 Deactivated<br />

1 Activated for drive control<br />

2 Activated for external application<br />

P9.2 118 — PID controllers, P gain 100<br />

0–1000% Proportional Gain (KP)<br />

Low values attenuate the control action<br />

High values can cause oscillation<br />

P9.3 119 — PID controller, I reset time 10.0<br />

0–320s Integral time constant<br />

P9.4 167 — PID controller, keypad reference 0.0<br />

0–100% Setting range<br />

P9.5 332 — PI controller, setpoint source 0<br />

0 The setting range is limited by P6.3 (raised starting frequency)<br />

and P6.4 (end frequency)<br />

Keypad (P9.4)<br />

1 Fieldbus<br />

2 AI1<br />

3 AI2<br />

Factory Setting<br />

(P1.3)<br />