Parameters<br />
Logic Function, continued<br />
PNU ID<br />
Access<br />
RUN Value/Range Description<br />
24 LOG function fulfilled<br />
Message if the logical operation of P13.3 is fulfilled (LOG = 1)<br />
25 PID controller, actual value monitoring<br />
Message if the actual value is within the hysteresis set at P9.15<br />
and P9.16<br />
26 External brake actuated<br />
Switch threshold: set value of P12.8<br />
27 Current monitoring<br />
Switch threshold: set value of P5.8<br />
28 Fieldbus, Remote output<br />
The number of the assigned digital output is written directly to<br />
the control word (ID2001, bit 13)<br />
P13.2 1454 X — LOG function, Selection input B 0<br />
Like P13.1 —<br />
P13.3 1455 X — LOG function, select operation<br />
Logical operation (LOG) of the selected functions of<br />
parameter P13.1 (A) and P13.2 (B)<br />
0<br />
Signal Logic Link (LOG)<br />
XOR<br />
A B AND OR (Exclusive or)<br />
0 0 0 0 0<br />
0 1 0 1 1<br />
1 0 0 1 1<br />
1 1 1 1 0<br />
The result of the logic operation (LOG) can be assigned to one<br />
of the three digital outputs (DO = P5.3), RO1 = P5.1 and<br />
RO2 = P5.2 with the value 24, or called via the serial interface<br />
(RS485, Modbus RTU) or an optional fieldbus connection<br />
(CANopen, PROFIBUS DP)<br />
0 A AND B<br />
1 A OR B<br />
2 A XOR B, exclusive A or B<br />
118 M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com<br />
Factory Setting<br />
(P1.3)