M-Maxâ„¢ Series Adjustable Frequency Drive - Eaton Corporation
M-Maxâ„¢ Series Adjustable Frequency Drive - Eaton Corporation
M-Maxâ„¢ Series Adjustable Frequency Drive - Eaton Corporation
Create successful ePaper yourself
Turn your PDF publications into a flip-book with our unique Google optimized e-Paper software.
Appendix A<br />
Motor<br />
Access<br />
FS<br />
PNU ID RUN ro/rw Designation Value Range Page (P1.3)<br />
P7.1 113 X rw Motor, rated current 0.2 x Ie –2 x Ie (see motor rating plate)<br />
87 Ie P7.2 107 X rw Current limit 0.2 x Ie –2 x Ie 87 1.5 x Ie P7.3 112 X rw Motor, rated speed 300–20000 min –1<br />
(see motor rating plate)<br />
87<br />
�<br />
P7.4 120 X rw Motor, power factor (cos ) 0.30–1.00<br />
(see motor rating plate)<br />
P7.5 110 X rw Motor, rated operating voltage 180–500V<br />
(see motor rating plate)<br />
P7.6 111 X rw Motor, rated frequency 30–320 Hz<br />
(see motor rating plate)<br />
Protective Functions<br />
Note<br />
� Factory settings dependent on specific drive selected.<br />
156 M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com<br />
87<br />
87<br />
�<br />
�<br />
87 60.00<br />
Access<br />
FS<br />
PNU ID RUN ro/rw Designation Value Range Page (P1.3)<br />
P8.1 700 X rw Analog minimum reference error 0 = Deactivated<br />
88 1<br />
(live-zero)<br />
1 = Alarm<br />
2 = Fault, stop according to P6.8<br />
P8.2 727 X rw Undervoltage error Like P8.1 88 2<br />
P8.3 703 X rw Ground fault Like P8.1 88 2<br />
P8.4 709 X rw Stall protection Like P8.1 89 1<br />
P8.5 713 X rw Underload protection Like P8.1 89 0<br />
P8.6 704 X rw Motor, temperature protection Like P8.1 89 2<br />
P8.7 705 X rw Motor, ambient temperature –20° to 100°C 89 40<br />
P8.8 706 X rw Motor, cooling factor at<br />
zero frequency<br />
0.0–150% 89 40<br />
P8.9 707 X rw Motor, thermal time constant 1–200 min 89 45<br />
P8.10 1430 X rw Analog minimum reference error 0.0–10.0s 91 0.5<br />
P8.11 1473 X — (Not used) — — —<br />
P8.12 714 X rw Underload low torque limit at<br />
zero frequency<br />
10.0–150% 91 60.0<br />
P8.13 715 X rw Underload low torque limit 10.0–150% 91 10.0<br />
P8.14 733 X rw Fieldbus error Like P8.1 92 2<br />
P8.15 734 X rw Fieldbus interface error Like P8.1 92 2<br />
User<br />
Setting<br />
User<br />
Setting