Appendix A<br />

All Parameters<br />

When first switching on or after activating the default settings (S4.2 = 1) parameter P1.1 must<br />

be set to 0 for access to all parameters.<br />

Parameter Selection<br />

Access<br />

FS<br />

PNU ID RUN ro/rw Designation Value Range Page (P1.3)<br />

P1.1 115 rw Quick start parameters 0 = All parameters<br />

1 = Only quick configuration<br />

parameters<br />

65/64 1<br />

P1.2 540 X rw Application 0 = Basic<br />

1 = Pump drive<br />

2 = Fan drive<br />

3 = High load<br />

P1.3 1472 X rw Country specific default<br />

settings (FS)<br />

Analog Input<br />

0 = EU<br />

1 = USA<br />

150 M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com<br />

65 0<br />

65 0<br />

Access<br />

FS<br />

PNU ID RUN ro/rw Designation Value Range Page (P1.3)<br />

P2.1 379 rw AI1, signal range (microswitch S2)<br />

0 = 0–10V/0–20 mA<br />

1 = 2–10V/4–20 mA<br />

66 0<br />

P2.2 380 rw AI1 custom min –100.00 to 100.00% 66 0<br />

P2.3 381 rw AI1 custom max –100.00 to 100.00% 66 100<br />

P2.4 378 rw AI1 filter time 0.0–10.0s 66 0.1<br />

P2.5 390 rw AI2, signal range (microswitch S3)<br />

Like P2.1<br />

67 1<br />

P2.6 391 rw AI2 custom min –100.00 to 100.00% 67 0<br />

P2.7 392 rw AI2 custom max –100.00 to 100.00% 67 100<br />

P2.8 389 rw AI2 filter time 0.0–10.0s 67 0.1<br />