Parameters<br />

Quick Start Parameter Guide<br />

The following table shows the preset application parameters of parameter P1.2. in the factory setting.<br />

With P1.1 = 1 you are guided through the drive parameters in steps (Quickstart Wizard) after the power<br />

supply is switched on and after the factory settings are activated.<br />

Predefined Application Parameters from Parameter P1.2<br />

Parameter<br />

(PNU)<br />

P1.1 1 = Only quick<br />

configuration<br />

parameters<br />

Basic<br />

(Standard <strong>Drive</strong>) Pump <strong>Drive</strong> Fan <strong>Drive</strong> High Load Designation<br />

Notes<br />

� 230V = MMX11_, MMX12_, MMX32_.<br />

400V = MMX34_, 575V = MMX35_.<br />

1 = Only quick<br />

configuration<br />

parameters<br />

1 = Only quick<br />

configuration<br />

parameters<br />

1 = Only quick<br />

configuration<br />

parameters<br />

64 M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com<br />

Quick start parameters<br />

P1.2 0 = Basic 1 = Pump drive 2 = Fan drive 3 = Hoisting device<br />

(high load)<br />

Application<br />

P1.3 0 = EU 0 = EU 0 = EU 0 = EU Country specific default<br />

settings<br />

P6.1 1 = Control signal<br />

terminals (I/O)<br />

(I/O)<br />

P6.2 3 = AI1 (analog<br />

setpoint 1)<br />

1 = Control signal<br />

terminals (I/O)<br />

(I/O)<br />

3 = AI1 (analog<br />

setpoint 1)<br />

1 = Control signal<br />

terminals (I/O)<br />

(I/O)<br />

3 = AI1 (analog<br />

setpoint 1)<br />

1 = Control signal<br />

terminals (I/O)<br />

(I/O)<br />

3 = AI1 (analog<br />

setpoint 1)<br />

Primary remote control<br />

source<br />

Primary remote speed<br />

reference<br />

P6.3 0.00 Hz 20.00 Hz 20.00 Hz 0.00 Hz Minimum frequency<br />

P6.4 50.00 Hz 50.00 Hz 50.00 Hz 50.00 Hz Maximum frequency<br />

P6.5 3.0s 5.0s 20.0s 1.0s Acceleration time (acc1)<br />

P6.6 3.0s 5.0s 20.0s 1.0s Deceleration time (dec1)<br />

P6.7 0 = Ramp<br />

0 = Ramp<br />

0 = Ramp<br />

0 = Ramp<br />

Start function<br />

(acceleration) (acceleration) (acceleration) (acceleration)<br />

P6.8 0 = Free coasting 1 = Deceleration<br />

time (ramp)<br />

0 = Free coasting 0 = Free coasting Stop function<br />

P7.1 Ie Ie Ie Ie Motor, rated current<br />

P7.3 1440 RPM 1440 RPM 1440 RPM 1440 RPM Motor, rated speed (RPM)<br />

P7.4 0.85 0.85 0.85 0.85 Motor, power factor<br />

(cos )<br />

P7.5 230/400/575V � 230/400/575V � 230/400/575V � 230/400/575V � Motor, rated operating<br />

voltage<br />

P7.6 60 Hz 60 Hz 60 Hz 60 Hz Motor, rated frequency<br />

P11.7 0 = Deactivated 0 = Deactivated 0 = Deactivated 1 = Enabled Torque increase<br />

M1.1 0.00 Hz 0.00 Hz 0.00 Hz 0.00 Hz Output frequency<br />

(display only)