Serial Interface (Modbus RTU)<br />
Modbus Parameters<br />
The following table shows the Modbus parameters in the M-Max.<br />
RUN Indicates the access during operation (FWD or REV)<br />
X = No parameter change possible,<br />
= Parameter change possible.<br />
Modbus Parameters in the M-Max<br />
Access<br />
130 M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com<br />
ro/rw Indicates the access via the fieldbus<br />
ro = Read only possible,<br />
rw = Read and write possible.<br />
PNU ID RUN ro/rw Designation Value Range<br />
S2.1 808 � X ro Communication status Format xx.yyy<br />
xx = Number of received faulty messages (0–64)<br />
yyy = Number of received correct messages (0–999)<br />
S2.2 809 � rw Fieldbus protocol 0 = Fieldbus deactivated<br />
1 = Modbus<br />
S2.3 810 � rw Slave address 1–255 1 �<br />
S2.4 811 � rw Baud rate 0 = 300<br />
1 = 600<br />
2 = 1200 (1.2k Baud)<br />
3 = 2400 (2.4k Baud)<br />
4 = 4800 (4.8k Baud)<br />
5 = 9600 (9.6k Baud)<br />
6 = 19200 (19.2k Baud)<br />
7 = 38400 (38.4k Baud)<br />
8 = 57600 (57.6k Baud)<br />
S2.6 813 rw Parity type 0 = None l 2 Stop bits<br />
1 = Even l 1 Stop bit<br />
2 = Odd l 1 Stop bit<br />
S2.7 814 rw Timeout up to fieldbus<br />
error (error 53) if no<br />
master messages are<br />
received although<br />
Modbus is still active.<br />
S2.8 815 rw Reset communication<br />
status<br />
xx and yyy are reset to 0<br />
0 = Not used<br />
1 = 1s<br />
2 = 2s<br />
...255 = up to 255s<br />
0 = Not used<br />
1 = resets parameter S2.1<br />
<strong>Drive</strong>s Control<br />
P6.1 125 rw Control place 1 1 = Control signal terminals (I/O)<br />
2 = Control unit (KEYPAD)<br />
3 = Interface (BUS)<br />
P6.2 117 rw Setpoint Source 0 = Fixed frequency (FF0)<br />
1 = Control unit (KEYPAD)<br />
2 = Interface (BUS)<br />
3 = AI1 (analog setpoint 1)<br />
4 = AI2 (analog setpoint 2)<br />
Note<br />
� When the fieldbus is connected (option, for example, CANopen, PROFIBUS DP, and so on) modified ID numbers and different factory settings are stored here.<br />
Detailed information is provided in the specific manuals of the relevant fieldbus interface module.<br />
FS<br />
(P1.3)<br />
0.000 �<br />
0 �<br />
5 �<br />
0<br />
0<br />
0<br />
1<br />
3