Parameters<br />

Protective Functions (P8)<br />

In parameter group P8, you can set the reaction of the frequency inverter to external<br />

influences and increase the protection to the drive system (PDS):<br />

● 0 = deactivated, no reaction<br />

● 1 = Alarm (for example, AL 50)<br />

● 2 = Fault (stop mode after error message based on parameters P6.8, for example, F…50)<br />

The (FAULT) and (ALARM) messages are described on Page 54.<br />

Protective Functions<br />

PNU ID<br />

Access<br />

RUN Value/Range Description<br />

P8.1 700 X — Analog minimum reference error (live-zero)<br />

Monitors the live zero of the analog inputs AI1 and AI2 if the<br />

parameters P2.1 and P2.5 are set to 1 (4 mA, 2V):<br />

AI1, control signal terminal 2, P2.1<br />

AI2, control signal terminal 4, P2.5<br />

A warning or error message (F… 50) is output if the signal drops<br />

below 3.0 mA or 1.5V for 5 seconds or 0.5 mA or 0.25V for<br />

0.5 seconds. This reaction time can be changed at P8.10<br />

1<br />

0 Deactivated<br />

1 Alarm (AL 50)<br />

Note: If the setpoint is restored ( 4 mA, 2V) the drive starts<br />

up automatically if there is no disconnection by the warning<br />

message<br />

2 Fault (F… 50), stop function according to P6.8<br />

P8.2 727 X — Undervoltage error<br />

Under-voltage error in the intermediate circuit because of a low<br />

input-side supply voltage, for example, by connecting 230V to a<br />

400V device or if a phase drops out<br />

2<br />

0 Deactivated<br />

1 Alarm (AL 09)<br />

Note: A start signal (START button, rising edge on the control<br />

terminals) must exist again for restarting<br />

2 Fault (F… 09), stop function according to P6.8<br />

P8.3 703 X — Ground fault<br />

The ground fault monitoring checks the currents in the motor<br />

phases and is continually active. It protects the frequency<br />

inverter from ground faults with high currents<br />

2<br />

0 Deactivated<br />

If the monitoring is deactivated, the reaction time is shortened<br />

to a start signal<br />

Caution: When the monitoring is deactivated, a ground fault<br />

can cause damage to the inverter<br />

1 Alarm (AL 03)<br />

2 Fault (F… 03), stop function according to P6.8<br />