The following examples show two practical applications for<br />

the second parameter set.<br />

Example 1<br />

Roller conveyor with rotary table:<br />

● Motor M1 (0.75 kW) drives the rollers on the rotary table<br />

and transports the goods further<br />

● Motor M2 (1.5 kW) rotates the table for the alternating<br />

acceptance of goods from two feed lines<br />

Roller Conveyor with Rotary Table<br />

For alternating operation (rotary movement “exclusive or” of<br />

the transport rollers) on the rotary table, a frequency inverter<br />

for the largest connected load (MMX34AA4D3_) was<br />

selected.<br />

The different rating data of the motors were set in the<br />

parameter groups P7 (for motor M1) and P14 (for motor M2).<br />

The second parameter set (P14) is activated here as an<br />

example via digital input DI6 (P3.27 = 6).<br />

The change between the two motors is implemented in this<br />

example via contactors Q11 (M1) and Q12 (M2) at standstill.<br />

The enabling and selection of the relevant parameter group is<br />

activated via the digital inputs:<br />

M<br />

3<br />

● Motor M1 = DI1 (FWD, control signal terminal 8) operation<br />

with parameter group P7<br />

● Motor M2 = DI1 (FWD, control signal terminal 8) and DI6<br />

(2PS, control signal terminal 16) operation with parameter<br />

group P14 (second parameter set)<br />

˜<br />

M<br />

3<br />

˜<br />

M1<br />

M2<br />

F1<br />

Q11<br />

M1<br />

Q12<br />

F2<br />

U1 V1 W1 U1 V1 W1<br />

M<br />

3<br />

˜<br />

24V<br />

M2<br />

Parameters<br />

During maintenance and setting work the following applies<br />

for reversing duty:<br />

● Motor M1 = DI2 (REV, control signal terminal 9) operation<br />

with parameter group P7<br />

● Motor M2 = DI2 (REV, control signal terminal 9) and DI6<br />

(2PS, control signal terminal 16) operation with parameter<br />

group P14 (second parameter set)<br />

Digital input DI6 is assigned in the factory setting (P3.12 = 6)<br />

with the function PI-OFF (PID controller, deactivated). Setting<br />

P3.12 = 0 is used to switch off this function of DI6. Setting<br />

P3.27 = 6 enables the second parameter set (2PS) function<br />

to be assigned to digital input DI6.<br />

M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com 121<br />

M<br />

0.75 kW 1.5 kW<br />

6<br />

+24V Out<br />