Parameters<br />

Logic Function (P13)<br />

The logic function enables you to link both parameters P13.1 (A) and P13.2 (B) logically with<br />

each other. The result (LOG) can then be assigned to the digital outputs DO (P5.3), RO1 (P5.1)<br />

and RO2 (P5.2). The type of operation (And, Or, Exclusive-Or) is defined in parameter P13.3.<br />

Logic Linking of A and B<br />

0<br />

1<br />

...<br />

28<br />

0<br />

1<br />

...<br />

28<br />

P13.1<br />

P13.2<br />

A<br />

B<br />

A AND B<br />

A OR B<br />

A XOR B<br />

Example: Digital output RO1 (N/O contact R13/R14) is required to indicate during operation<br />

that the set current limit has been reached:<br />

P5.1 = 24, LOG function fulfilled<br />

P13.1 = 2, Operation (RUN), signal A<br />

P13.2 =27, Current monitoring, signal B<br />

P13.3 = 0, A AND B<br />

0<br />

1<br />

2<br />

P13.3<br />

116 M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com<br />

LOG<br />

24<br />

24<br />

24<br />

P5.3<br />

P5.1<br />

P5.2<br />

DO1<br />

RO1<br />

RO2<br />

DO+<br />

DO–<br />

R13<br />

R14<br />

R21<br />

R22<br />

R24<br />

20<br />

13<br />

22<br />

23<br />

25<br />

24<br />

26

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!