Logic Function<br />

PNU ID<br />

Access<br />

RUN Value/Range Description<br />

P13.1 1453 X — LOG function, Selection input A<br />

Value range for signal A<br />

0<br />

0 Deactivated<br />

1 READY, the frequency inverter is ready for operation<br />

2 RUN, the inverter of the frequency inverter is enabled<br />

(FWD, REV)<br />

3 FAULT, error message<br />

Error detected (= STOP)<br />

4 Error message inverted (no error message)<br />

5 ALARM, warning message<br />

(see “Protective Functions (P8)” on Page 88)<br />

6 REV (Reverse run), anticlockwise rotating field active<br />

7 Output frequency = frequency setpoint<br />

8 Motor controller active<br />

9 Zero frequency<br />

Output frequency = 0 (Hz)<br />

10 <strong>Frequency</strong> monitoring 1<br />

For the frequency ranges set at P5.4 and P5.5<br />

11 <strong>Frequency</strong> monitoring 2<br />

For the frequency ranges set at P5.6 and P5.7<br />

12 PID monitoring<br />

For the deviation set at P9.17<br />

13 Overtemperature signal<br />

14 Overcurrent control active<br />

15 Overvoltage control active<br />

16 PLC Sequence control active<br />

17 PLC Sequence control, single step completed<br />

18 PLC Sequence control, program cycle completed<br />

19 PLC Sequence control, pause<br />

20 Counter, value 1 reached<br />

The counter value is the trigger value set at P3.21 and<br />

21<br />

can be reset by activating P3.24<br />

Counter, value 2 reached<br />

The counter value is the trigger value set at P3.22 and<br />

22<br />

can be reset by activating P3.24<br />

RUN message active<br />

23 Analog minimum reference error<br />

Message, AL 50 if the value of AI1 and/or AI2 goes below<br />

the 4 mA or 2V setpoint value (live zero) (P2.1 = 1, P2.5 = 1)<br />

Values continued on next page<br />

Parameters<br />

Factory Setting<br />

(P1.3)<br />

M-Max <strong>Series</strong> <strong>Adjustable</strong> <strong>Frequency</strong> <strong>Drive</strong> MN04020003E—April 2011 www.eaton.com 117