Logic Function<br />
PNU ID<br />
Access<br />
RUN Value/Range Description<br />
P13.1 1453 X — LOG function, Selection input A<br />
Value range for signal A<br />
0<br />
0 Deactivated<br />
1 READY, the frequency inverter is ready for operation<br />
2 RUN, the inverter of the frequency inverter is enabled<br />
(FWD, REV)<br />
3 FAULT, error message<br />
Error detected (= STOP)<br />
4 Error message inverted (no error message)<br />
5 ALARM, warning message<br />
(see “Protective Functions (P8)” on Page 88)<br />
6 REV (Reverse run), anticlockwise rotating field active<br />
7 Output frequency = frequency setpoint<br />
8 Motor controller active<br />
9 Zero frequency<br />
Output frequency = 0 (Hz)<br />
10 <strong>Frequency</strong> monitoring 1<br />
For the frequency ranges set at P5.4 and P5.5<br />
11 <strong>Frequency</strong> monitoring 2<br />
For the frequency ranges set at P5.6 and P5.7<br />
12 PID monitoring<br />
For the deviation set at P9.17<br />
13 Overtemperature signal<br />
14 Overcurrent control active<br />
15 Overvoltage control active<br />
16 PLC Sequence control active<br />
17 PLC Sequence control, single step completed<br />
18 PLC Sequence control, program cycle completed<br />
19 PLC Sequence control, pause<br />
20 Counter, value 1 reached<br />
The counter value is the trigger value set at P3.21 and<br />
21<br />
can be reset by activating P3.24<br />
Counter, value 2 reached<br />
The counter value is the trigger value set at P3.22 and<br />
22<br />
can be reset by activating P3.24<br />
RUN message active<br />
23 Analog minimum reference error<br />
Message, AL 50 if the value of AI1 and/or AI2 goes below<br />
the 4 mA or 2V setpoint value (live zero) (P2.1 = 1, P2.5 = 1)<br />
Values continued on next page<br />