<strong>Drive</strong>s Control, continued<br />

PNU ID<br />

Access<br />

RUN Value/Range Description<br />

P6.10 717 X — REAF, Wait time before an automatic restart 0.50<br />

0.10–10.00s Active, if P6.13 = 1<br />

Waiting time until automatic restart, after the detected<br />

error has disappeared<br />

(REAF = Restart After Failure)<br />

P6.11 718 X — REAF, Testing period over three automatic restarts 30.00<br />

0.00–60.00s Active, if P6.13 = 1<br />

Timed monitoring of the automatic restart<br />

The monitoring time begins with the first automatic restart.<br />

If more than three error messages occur during the testing<br />

period, fault status is activated. Otherwise, the error is<br />

acknowledged after the test time has elapsed and the test<br />

time is only started again with the next error<br />

P6.12 719 X — REAF, Start function with automatic restart 0<br />

0 Ramp (acceleration)<br />

1 Flying restart circuit<br />

2 According to P6.7<br />

P6.13 731 X — REAF, automatic restart after an error message 0<br />

0 Deactivated<br />

1 Activated<br />

P6.14 1600 — Stop on direction change via the arrow buttons () of the 1<br />

keypad (KEYPAD)<br />

0 Deactivated, changes the direction of rotation (FWD<br />

automatically on passing setpoint zero<br />

REV)<br />

1 Activated, stops the drive at setpoint zero and requires<br />

another actuation of the Start button<br />

Automatic Restart After Error Message<br />

(Two Start Attempts)<br />

START<br />

TEST<br />

FAULT<br />

RESET<br />

P6.10<br />

P6.10 P6.10<br />

P6.11<br />

Item<br />

Number Description<br />

1 First automatic restart<br />

2 Second automatic restart<br />

3 Shut-off when error detected<br />

4 Motor stop signal<br />

TEST = monitored test tim<br />

FAULT = shut-off when error message occurs<br />

RESET = reset error message (FAULT)<br />