3.9.2 What You Should Know About GSD Revisions<br />

<strong>Configuring</strong> the Distributed I/O (DP)<br />

The properties of DP slaves are provided to configuration tools by means of<br />

GSD files.<br />

Any extended functions for distributed I/O devices will have an effect on the<br />

GSD specification, such as resulting in the definition of new keywords.<br />

This results in their being different versions of the specification. The version of the<br />

specification that a GSD file interacts with is called "GSD-Revision".<br />

The GSD revision is contained as an obligatory keyword "GSD_Revision" in<br />

GSD files as of GSD Revision 1. GSD files lacking this keyword will be thus be<br />

interpreted by configuration tools as GSD Revision "0".<br />

<strong>STEP</strong> 7 V5.1, Service Pack 3<br />

This version of <strong>STEP</strong> 7 can interpret GSD files up to GSD Revision 4. This means<br />

that you can also use the following new functions for DP slaves that are installed by<br />

means of GSD (Revision 4):<br />

• F-parameter assignment of submodules<br />

• Diagnostic messages for interrupt blocks<br />

• Constant mode (isochrone mode)<br />

Special Features:<br />

Please note that the optional package COM PROFISafe must be installed to edit Fparameters.<br />

If this package is not installed, the parameters will not be visible <strong>and</strong><br />

thus cannot be changed. The F-parameters will, however, remain (default values<br />

are taken from the GSD file or are values changed with COM PROFISafe) <strong>and</strong> will<br />

be taken into account when generating a configuration (For further information, see<br />

the documentation on distributed F-systems).<br />

The following functions, although possible in GSD Revision 4, are not supported:<br />

• A second parameter frame (extended parameter assignment)<br />

• Subscriber functions (receive capability for direct data exchange/lateral<br />

communication)<br />

• Keywords for HART parameter assignment<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

A5E00706939-01 3-55

Hooray! Your file is uploaded and ready to be published.

Saved successfully!

Ooh no, something went wrong!