<strong>Configuring</strong> the Distributed I/O (DP)<br />

3.6.3 ET 200S with Option H<strong>and</strong>ling<br />

Requirements for Option H<strong>and</strong>ling<br />

• Power submodule: PM-E DC 24V/AC120/230V or PM-E DC 24..48V/AC<br />

120..230V with option h<strong>and</strong>ling (as of <strong>STEP</strong> 7 V5.3)<br />

• Interface submodule: IM 151-1 STANDARD (6ES7 151-1AA03-0AB0) or IM<br />

151-1 FO STANDARD (6ES7 151-1AB02-0AB0)<br />

Overview of the Procedure<br />

Rules<br />

Option h<strong>and</strong>ling allows you to prepare the ET 200S for future expansions (options).<br />

The following section provides overview of the function <strong>and</strong> procedure (for a<br />

detailed description, see the ET 200S Distributed I/O manual):<br />

1. Install, wire, configure <strong>and</strong> program the planned maximum configuration for<br />

ET 200S.<br />

2. Instead of using the electronic submodules that will be required later, use<br />

economical RESERVE submodules (138-4AA00 or 138-4AA10) for the first<br />

installation. The ET 200S can be completely prewired ("master wiring")<br />

because a RESERVE submodule is not connected to the terminals of the<br />

terminal submodule <strong>and</strong> thus is not involved in the process.<br />

3. For those slots that will first be fitted with RESERVE submodules instead of<br />

electronic submodules, enable option h<strong>and</strong>ling (in the property sheet for the IM<br />

151-1 STANDARD, go to the "Option H<strong>and</strong>ling" tab).<br />

4. In the property sheet for the power submodule, reserve the required address<br />

space in the process image output table (PIQ) <strong>and</strong> the process image input<br />

table (PII) for the control <strong>and</strong> feedback interface by enabling option h<strong>and</strong>ling.<br />

5. Later on, you can replace the RESERVE submodules with the configured<br />

submodules without having to repeat the configuration procedure.<br />

Option h<strong>and</strong>ling may be enabled for exactly one PM E-DC24..48V or PM<br />

EDC24..48V/AC24.. power submodule.<br />

Functionality: Option H<strong>and</strong>ling During Start-up<br />

If "Startup when defined <strong>and</strong> actual configuration differ" is disabled, then the<br />

ET 200S will also start up if a RESERVE module is inserted instead of the<br />

configured electronic submodule <strong>and</strong> option h<strong>and</strong>ling is enabled for the slot.<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

3-20 A5E00706939-01