Interrupts for Modules with Packed Addresses<br />

<strong>Configuring</strong> the Distributed I/O (DP)<br />

If the submodule can trigger interrupts <strong>and</strong> its addresses are packed (that is, it has<br />

a bit address not equal to 0), then you must use the ET 200S address dialog to<br />

assign a dialog address.<br />

The diagnostic address is essential to assigning a DPV1 interrupt to the submodule<br />

as the interrupt trigger. Only when a submodule has this "unpacked address" can<br />

the CPU assign an interrupt <strong>and</strong> store information about the interrupt in the start<br />

information for the interrupt OB or in the diagnostic buffer. The CPU cannot use a<br />

"packed" address to do this.<br />

This diagnostic address assigned to the submodule is only valid for interrupt<br />

processing (interrupt OB). For processing input <strong>and</strong> output data in the user<br />

program, the submodule still has the packed addresses.<br />

Note<br />

If the submodule addresses are packed, then the insert/remove interrupt for the<br />

ET 200S is also disabled!<br />

3.6.5 ET 200iS<br />

Configuration<br />

You can either configure ET 200iS <strong>and</strong> its electronic modules in the HW Config or<br />

conveniently do so with the SIMATIC PDM option package The respective system<br />

requirements <strong>and</strong> procedure are described below:<br />

System Requirement<br />

<strong>STEP</strong> 7 as of version 5.1, SP 2, Hotfix 1 or PCS7 as of version 5.2.<br />

In this case, ET 200iS is in the <strong>STEP</strong> 7 hardware catalog. Diagnostic interrupts,<br />

process interrupts, inserting <strong>and</strong> removing interrupts <strong>and</strong> time stamps are<br />

supported.<br />

<strong>Configuring</strong> the ET 200iS<br />

1. Start the SIMATIC Manager.<br />

2. Configure ET 200iS with HW Config.<br />

- Create new project.<br />

- Drag <strong>and</strong> drop the module from the hardware catalog to the configuration<br />

table.<br />

3. Configure the time stamping (optional).<br />

4. Save or download the configuration to the DP master.<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

A5E00706939-01 3-23