4.2.3 Creating a PROFINET IO System<br />

Requirement<br />

<strong>Configuring</strong> PROFINET IO Devices<br />

You have arranged a module rack in the station window, <strong>and</strong> it is now opened<br />

(slots in the rack are visible).<br />

PROFINET IO Controller<br />

You can use the following devices as an IO controller:<br />

• A CPU with an integral or insertable PROFINET interface (integral, such as<br />

CPU 317-2 PN/DP)<br />

• A CP along with a CPU (e.g. CP 443-1 Advanced connected to a suitable<br />

S7-400-CPU)<br />

• A PC station (e.g. with CP 1612)<br />

Procedure<br />

1. In the "<strong>Hardware</strong> Catalog" window, select an IO controller (e.g. CPU 317-2<br />

PN/DP).<br />

2. Drag-<strong>and</strong>-drop the module to a permissible row in the module rack. The<br />

"Properties – Ethernet Node" dialog box then opens.<br />

Here you can do the following:<br />

- Create a new Ethernet subnet or select <strong>and</strong> existing one<br />

- Set the properties for the Ethernet subnet (such as the name)<br />

- Set the IP address of the IO controller<br />

3. Confirm the settings with "OK"<br />

The following symbol appears for CPUs with an integral IO controller:<br />

This symbol is the "peg board" for the IO devices in the IO system.<br />

External IO Controllers<br />

CPs that can be used as external IO controllers support numerous options for<br />

communications. As such, they are not "predetermined" for use as IO controllers.<br />

If you use an external IO controller (e.g. CP 443-1 Advanced), then you have to<br />

insert an IO system after inserting the IO controller (context menu comm<strong>and</strong>:<br />

"Insert PROFINET IO System").<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

A5E00706939-01 4-15