14.6 Downloading a Changed HW Configuration to an<br />

S7-400H Station<br />

Downloading<br />

With an H-station, you can download a changed HW configuration, without the Hstation<br />

having to go in STOP mode. To ensure that the H-station can modify the<br />

process without interruption during the download; that is, that one of the two CPUs<br />

is always in RUN mode, you must absolutely follow the prescribed sequence of<br />

operations. For a complete, detailed description of the functions <strong>and</strong> procedures,<br />

refer to the following manual: Automation System S7-400H Fault-Tolerant<br />

Systems.<br />

As of <strong>STEP</strong> 7 V5.3 Service Pack 2, you have the option of letting the download<br />

procedure after changing the hardware configuration run almost completely<br />

automatically. <strong>STEP</strong> 7 will automatically prepare the next action required. To have<br />

this action carried out, you will only have to confirm the step by clicking the "Next"<br />

button.<br />

You can also configure this function so that the switchover from one CPU to the<br />

other happens mostly automatically.<br />

Requirements <strong>and</strong> Restrictions for an Automatic Download<br />

• Downloading a changed HW configuration to an S7-400 H-station can only be<br />

done in HW Config.<br />

• The changed configuration can only be downloaded to CPUs. The configuration<br />

will not be downloaded to any modules that receive their configuration data<br />

directly (FM 456-2, FM 456-4).<br />

• When downloading, you cannot reconfigure node addressees; the node<br />

addresses configured for the H-CPUs must match the existing node addresses.<br />

• At least one of the two H-CPUs must be able to be reached online.<br />

• The H-station does not necessarily have to be in redundant mode; it is sufficient<br />

to have one of the CPUs in RUN mode. For an automated download, the Hstation<br />

will be placed in redundant mode when the reserve CPU is restarted.<br />

• The operating mode switch for both CPUs must be in RUN position (RUN-P for<br />

CPUs with a keyswitch).<br />

If all of these requirements are not met, then the "Download station configuration in<br />

RUN mode" option will not be available.<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

A5E00706939-01 14-9