<strong>Configuring</strong> PROFINET IO Devices<br />

4.4.5 Changing the IP-Address or the Device Name During Operation<br />

Assigning an IP address or device name for a single node<br />

Before a new IP address or a device name can be assigned, the following<br />

conditions must be met:<br />

There is no data being exchanged with the IO controller.<br />

If the SIMATIC Manager or the list of accessible nodes is open, you can assign<br />

each PROFINET-device an/another IP address another device name. To do this,<br />

select the PLC > Assign Ethernet Address menu comm<strong>and</strong>.<br />

Changing IP addresses from a central location<br />

If you have to check or change the IP addressees for several IO devices, proceed<br />

as follows:<br />

1. In HW Config, select the PROFINET IO system (the "railroad track") <strong>and</strong> then<br />

select Edit > PROFINET IO > PROFINET IO System > IP Addresses menu<br />

comm<strong>and</strong>. Alternative method: you can also find this function by selecting an<br />

IO system <strong>and</strong> then right-clicking to display the context menu.<br />

2. The dialog box that is then displayed shows all the IO devices with their current<br />

device names <strong>and</strong> IP addresses. You can change all the IP addresses from<br />

this central location.<br />

3. Download the changed IP addresses (menu comm<strong>and</strong>: PLC > Download to<br />

Module).<br />

When an IO controller or an IO device is selected, you can also call this function in<br />

NetPro by selecting the Edit > PROFINET IO > PROFINET IO System > IP<br />

Addresses menu comm<strong>and</strong>.<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

4-30 A5E00706939-01