<strong>Configuring</strong> the Distributed I/O (DP)<br />

Optimizing the Configuration<br />

To assist you in optimizing the configuration, the "Isochrone Mode" dialog box<br />

provides an overview of all clocking-related parameters. To open this dialog box,<br />

go to HW Config <strong>and</strong> select the Edit > Isochrone Mode menu comm<strong>and</strong>.<br />

The dialog box is divided into a hierarchy containing "PROFIBUS", "Slave" <strong>and</strong><br />

"Module" display areas. When you select a master system in the "PROFIBUS"<br />

area, the "Slave" area will automatically display the associated slaves. Similarly,<br />

when you select a DP slave, the "Module" area will automatically display the<br />

associated modules. For a detailed description of the columns displayed in the<br />

dialog box, see the relevant online help section.<br />

Creating a User Program<br />

Create the required synchronous cycle interrupt OBs (i.e. OB 61).<br />

At the start of the synchronous cycle interrupt OBs, the SFC 126 'SYNC_PI' must<br />

be called to update the process image partition for inputs, <strong>and</strong> at the end of OB 61,<br />

SFC 127 'SYNC_PO' must be called to update the process image partition for<br />

outputs. The process image partition to be used here is the one configured in the<br />

CPU ("Synchronous Cycle Interrupts" tab).<br />

Notes<br />

In particular, the following situation can arise with very short DP cycle times: The<br />

runtime of the user program (OB6x with SFC 126/127 called) is greater than the<br />

smallest cycle (see the technical data for the CPU, Section "Isochrone Mode"). In<br />

this case, you will have manually increase the DP cycle time that was automatically<br />

calculated by <strong>STEP</strong> 7.<br />

The runtime for individual OBs can be determined for different periods of time with<br />

SFC 78 'OB_RT' (WinAC RTX only).<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

3-90 A5E00706939-01