Requirements<br />

<strong>Configuring</strong> the Distributed I/O (DP)<br />

• The constant-bus-cycle-time master must support the "Constant bus cycle time"<br />

function (see info text in the hardware catalog).<br />

• The constant-bus-cycle-time master must be a class 1 DP master. This means<br />

a PG/PC can never be a constant-bus-cycle-time master.<br />

• The constant-bus-cycle-time master is the only active station on the<br />

PROFIBUS-DP. Only one DP master system may be present on the<br />

PROFIBUS subnet. Programming devices or PCs can also be connected.<br />

• Constant bus cycle time is possible only for the "DP" <strong>and</strong> "User-Defined" bus<br />

profiles.<br />

• CiR must not be configured.<br />

• No H-CPU may be connected to the PROFIBUS subnet.<br />

• The PROFIBUS subnet must not be a cross-project one.<br />

Time for DP Constant Bus Cycle Time<br />

<strong>STEP</strong> 7 calculates a recommended time for the "DP constant bus cycle time(ms)"<br />

based on:<br />

• The PROFIBUS configuration (number of configured nodes, number of<br />

programming devices etc.)<br />

• Other information for the calculation which can be specified as an option (for<br />

example, any additional not configured programming devices to be taken into<br />

account)<br />

You can correct this time but not below the calculated <strong>and</strong> displayed minimum<br />

value.<br />

Influence of Connected Active Nodes (PGs/PCs <strong>and</strong> I Slaves)<br />

A PG/PC must only be taken into account if it is connected directly to the<br />

PROFIBUS via its PROFIBUS interface. It does not need to be taken into account if<br />

it is connected via the multipoint interface of the CPU, as shown in the following<br />

figure.<br />

<br />

<br />

<br />

If intelligent DP slaves (for example, CPU 315-2DP) are connected, the time for the<br />

DP constant bus cycle should be calculated generously.<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

A5E00706939-01 3-79