<strong>Configuring</strong> the Distributed I/O (DP)<br />

Constant Bus Cycle Time Behavior<br />

!<br />

When recalculating times, <strong>STEP</strong> 7 recommends a value for the constant bus cycle<br />

time. This value is based on the configuration in question. However, you can<br />

change this value.<br />

When <strong>STEP</strong> 7 calculates this value for the constant bus cycle time, it includes in its<br />

calculation the user data traffic of the DP master as well as an allowance for a few<br />

errors that may possibly occur.<br />

<strong>STEP</strong> 7 also calculates a minimum value for the constant DP bus cycle time. The<br />

cycle time cannot fall below this value. When <strong>STEP</strong> 7 calculates the minimum<br />

value, it considers only the normal message frames for each bus cycle. If errors<br />

occur, there may be violations of the constant bus cycle time.<br />

Times that are longer than the recommended times are possible without any<br />

problems.<br />

Caution<br />

If you select times that are shorter than the time that the system recommends,<br />

under certain circumstances the communication of the additional active nodes that<br />

are connected to the PROFIBUS subnet is delayed, or, in the worst case, comes to<br />

a st<strong>and</strong>still. If you set values close to the minimum possible constant bus cycle<br />

time that is displayed, bus faults can cause the entire PROFIBUS subnet to be shut<br />

down in certain cases.<br />

Relationship: Constant Bus Cycle Time <strong>and</strong> SYNC/FREEZE<br />

For PROFIBUS-DP, if you configure both "constant bus cycle time" <strong>and</strong><br />

SYNC/FREEZE groups, note the following:<br />

• Group 8 must not be used (reserved for constant bus cycle time clock). If you<br />

configure the group assignment first <strong>and</strong> have assigned group 8, you can no<br />

longer set constant bus cycle time.<br />

• If you configure group 7 when the constant bus cycle time is set, you cannot<br />

use the SYNC or FREEZE functions for the slaves in this group.<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />