<strong>Configuring</strong> the Distributed I/O (DP)<br />

3.6.7 HART Modules<br />

Requirement:<br />

HART modules are analog modules to which HART transducers can be connected<br />

(HART=Highway Addressable Remote Transducer).<br />

HART modules are required for distributed use with the IM 153-2 (ET 200M).<br />

To assign parameters to the HART transducers, start the parameter assignment<br />

tool SIMATIC PDM<br />

SIMATIC PDM is installed on the programming device/PC.<br />

Representing HART Measuring Transducers<br />

The transducers for HART modules are represented as interface submodules in<br />

the configuration table.<br />

Example: The module is located in slot 4. The transducer for the first channel is<br />

then represented as slot 4.1.<br />

To start SIMATIC PDM:<br />

• Double-click one of the "slots" for HART transducers.<br />

As you can also use the SIMATIC PDM tool for assigning parameters to<br />

PROFIBUS-PA field devices, you can start it as follows:<br />

• Assign a PA field device to a PA master system by dragging & dropping it from<br />

the "<strong>Hardware</strong> Catalog" window, <strong>and</strong> then double-click this PA field device.<br />

3.6.8 <strong>Configuring</strong> Software Redundancy<br />

The configuration of a "warm st<strong>and</strong>by" system consists of:<br />

• Two S7 stations with one PROFIBUS-DP master interface each<br />

(each of these interfaces forms its own subnet)<br />

• One or more slaves with the property "can be used redundantly with active<br />

backplane bus" (e.g. ET 200Ms with IM 153-3) which are connected to both<br />

subnets.<br />

This configuration guarantees that the st<strong>and</strong>by station is able to take over the<br />

processing of the user program if one station (this is, one of the two DP masters)<br />

fails. The slaves that are connected to both stations are then controlled by the<br />

reserve station.<br />

<strong>Configuring</strong> <strong>Hardware</strong> <strong>and</strong> <strong>Communication</strong> <strong>Connections</strong> with <strong>STEP</strong> 7<br />

3-26 A5E00706939-01